5.6
Updating the software
|Data exchange|
The
Data exchange|
menu.
Make sure that a data carrier with suitable system file (e.g. kes5_1pc_422-105L.hex for the Mono unit and
kes6_2pc_422-106L.hex for the Duo unit) has been inserted.
|0.1 Software update|
In the menu, select the
Enter periodic password (can be obtained through the customer service - only valid for a few days!).
Confirm Perform software update with „OK".
A loading bar soon appears, which indicates the data transfer, after which the control unit restarts automatically.
|1.3 Control type|
Under
Note the revision status on the sticker on the inside of the control unit cover.
5.7
Data read-out
|Data exchange|
The
Data exchange|
menu.
Proceed as follows to export the logbook:
Make sure that a data carrier with free memory has been inserted.
Press the "ESC" key to open the
Confirm with „OK".
A csv file is generated on the data carrier. This can be opened with any text editor or spreadsheet program.
38 / 124
menu is only accessible if a data carrier has been inserted. The „ESC" key opens/closes the
check the new revision status.
menu is only accessible if a data carrier has been inserted. The „ESC" key opens/closes the
|0.1 Data read-out|
Installation and operating instructions
sub item.
menu.
|
|
016-328