EN iveo initial operation/Setting by radio
6.1.3. Manual setup-mode, deletion and manual setting of the end positions
in operation bottom position, top stop without release
When the movement is interrupted once, the system is in manual setupmode.
Important: A limit stop for the upper end limit is necessary!
First the lower end limit has to be runup to. From there move to one point which is
approx. 5 cm ahead of the upper limit stop without interruption.
Caution!
Only connect the radio motor that you wish to program to the mains. It is not possible
to program more than one motor at the same time.
Operation
6 s
or
3 s
or
3 s
1 s
Drive
Press the STOP button of the transmitter for 6 seconds. The
motor will switch to manual setting mode. Both limit
positions already set will be deleted.
Move the motor to the lower end position with the UP or
DOWN button.
Press the STOP button of the transmitter for 3 seconds.
The correct rotation direction assignment will be carried out
at the end of the end position setting.
Move in UP direction to up to 5 cm ahead of the upper limit
stop.
Press the STOP button of the transmitter for 3 seconds.
The end positions are now set and the rotation direction
assignment is correct. Perform a test run: The drive will
move against the upper limit stop now and will not relieve
there!
Press the PROG button at the transmitter.
The transmitter is now permanently programmed.
62