5 Protection functions and emergency operation

5.1 Protection functions

The base station is equipped with many protection functions for avoiding damage to the overall system.

5.1.1 Pump protection function

In order to avoid damage by longer standstill times, the pump is activated within pre-defined periods.
The LED "pump" lights up during these periods.

5.1.2 Valve protection function

During periods without valve activation (e. g. outside the heating period) all heating zones with logged-
in room control unit are activated in a cyclic way in order to avoid clogging of the valves.

5.1.3 Antifreeze protection function

Independent from the operating mode, every switching output is equipped with an antifreeze function.
As soon as a previously set antifreeze temperature (5...10°C) is fallen short of, the valves of the allocated
heating zone are activated until this temperature is reached. The antifreeze temperature can be set via
the MicroSD card, via the web surface of the Ethernet variant or via the service level of the RBG display
(parameter 161).
Note:
The antifreeze function for a heating zone is only active after setting the corresponding room control
unit to the stand-by mode.

5.1.4 Dew point monitoring

If the installation is equipped with a dew point sensor (provided by the customer), the valves of all heat-
ing zones are closed if dewing is detected in order to avoid damages due to humidity.
The dew point sensor input is only used during cooling operation.

5.2 Emergency operation

If the base station is unable to establish a radio connection to the room control unit allocated to the
heating zone after a set time has elapsed, emergency operation is activated automatically. In emergency
operation, the switching outputs at the base station are activated with a modified PWM cycle duration
(parameter 181) independent from the heating system in order to avoid complete cooling of the rooms
(in heating operation) or dewing (in cooling operation).