No. Parameters
183 Cycle duration PWM
cooling
Valve protection function
190 Duration until activation
191 Valve activation duration
Pump protection function
200 Duration until activation
201 Activation duration
210 First open function (FO)
220 Automatic switching
between summer and
winter time
230 Setback difference
temperature
MVHR control
240 MVHR installation connec-
ted to the system
Dew point sensor
250 Control direction of dew
point sensor input
Description
Control duration in cooling operation
Starting time after last activation
Valve activation duration (0= function deactivated)
Starting time after last activation
Activation duration (0 = function deactivated)
Activation of all switching outputs at power-up
If the conversion is activated, time adaptation is
performed automatically according to CET guide-
lines
In case of activation of the setback via the external
input
Control of a mechanical ventilation with heat reco-
very (MVHR) via the Ethernet interface Operation via
the room control units Display.
The control direction of the dew point sensor input
at the base is inverted via room control unit or
parameter file.
Unit
[%]
Standard: 0
[d]
Standard: 14
[min]
Standard: 5
[d]
Standard: 3
[min]
Standard: 5
[min]
Off=0
Standard: 10
Deactivated=0
Activated=1
Standard: 1
[K]
Standard: 2-0
Deactivated=0
Activated=1
Standard: 0
normal=0
inverted=1
Standard: 0
43