be suspended efficiently! Follow the bracket instructions in chapter 10. If the flue gas exhaust duct
passes along or through combustible walls or floors, the duct must be sufficiently far away from the
combustible material to prevent fire.
1.4 Think of your safety
If you smell gas, you must not under any circumstances:
– Ignite an appliance
– Touch electrical switches or telephone from the area in question
Take the following action:
– Switch off the gas and electricity
– Activate the operational emergency plan
– Evacuate the building if necessary
2.0 Installation
2.1 Positioning the appliance
After unpacking, check the appliance for damage. Check that the information relating to the type/
model and the electrical voltage is correct. Install the appliance and any accessories to a sufficiently
solid structure [2], taking into account the minimum free space required [1].
For GSX you should use the four M10-sized suspension points [21].
2.2 Positioning the flue gas exhaust system and air supply
The device only has the CE approval in combination with its flue gas system. The flue gas system
includes: single flue set vertical or horizontal, extension pipes and elbows. Table [4] indicates
which parts can be used per appliance type. The flue gas system must be installed according to the
instructions attached.
The extension pipes must be laid in parallel. In exceptional cases, for example with thick roofs or
walls, the roof or wall terminal may be extended concentrically by a maximum of 1 meter.
If a flue gas set is to be installed sideways to or through a flammable floor or wall, then there must
be a minimum air gap of 25 mm around the flue gas sets. This to prevent fire and / or scorch hazard.
The mentioned flue gas products are made of aluminum or stainless steel.
The combustion air inlet pipes may consist of the same materials as specified for the flue gas
discharge, but may also consist of materials mentioned in the table on pages 6-8. Other materials are
not allowed.
The maximum lenght of the flue gas system and combustion air inlet pipes is 6 meters and with 1x2
bends of 90°. Contact the manufacturer when exceeding the maximum discharge lenght.
The roof and wall pass-throughs supplied by the manufacturer are identified by the following item
numbers:
Appliance type
GSX 20/35
GSX 55/75/90
Roof pass-through C33
59 90 556
59 90 560
Wall pass-through C13
59 90 579
59 90 583