4 EN – Quick installation guide
Install the drive on the wall
See figure
A
on page 91.
Check the insulation of the input and motor cables and the
motor
Check the insulation of the input cable according to local regulations before
connecting it to the drive.
See figure
D
on page 93. Ground the motor cable shield at the motor end. For
minimal interference, make a 360-degree grounding at the cable lead-through, or
EN
keep the pig tail short.
Check the insulation of the motor cable and motor when the cable is disconnected
DA
from the drive, see figure
each phase conductor and the Protective Earth conductor using a measuring voltage
DE
of 1000 V DC. The insulation resistance of an ABB motor must exceed 100 Mohm
(reference value at 25 °C or 77 °F). For the insulation resistance of other motors,
ES
please consult the manufacturer's instructions. Note: Moisture inside the motor
casing will reduce the insulation resistance. If moisture is suspected, dry the motor
FI
and repeat the measurement.
FR

Connect the power cables

IT
See figures
C
and
motor cabling.
NL
1. Remove the front cover. IP21 units: Release the retaining clip with a screwdriver
(a) and lift the cover from the bottom outwards (b).
PT
2. IP21 units: Remove the cable entry box cover by undoing the mounting screws.
RU
3. Attach the residual voltage warning sticker in the local language next to the
control unit.
SV
4. Remove the side plates of the cable entry box.
TR
5. Remove the shroud on the power cable terminals by releasing the clips on the
sides with a screwdriver and lifting (a). Knock out holes for the cables (b).
CN
6. For frames R8 and R9: If parallel cables are installed, knock out the shrouds on
the power cable terminals for the cables to be installed.
7. Cut adequate holes into the rubber grommets. Slide the grommets onto the
cables. Prepare the cable ends. Slide the cables through the holes of the bottom
plate and attach the grommets to the holes.
8. Ground the cable shields 360 degrees under the grounding clamps.
9. Connect the twisted cable shields to the grounding terminals.
E
on page 93. Measure the insulation resistance between
F
on pages
92
and 93. Use symmetrical shielded cable for the