When unit is surrounded by walls
B
D
A
C
A L
or more
1
B L
or more
2
C Front
D Front panel
E Rear panel
Note:
•
Wall heights (H) of the front and the back sides shall be within
height of front panel and rear panel.
•
If the panel height is exceeded, add the "h" dimension of the
figure above to L
and L
in the table above.
1
2
Model
L
L
1
2
PUHY-P400
450
250
PUHY-P500
Example: When h is 100
The L
dimension becomes 450+100=550 mm.
1
When there is an obstruction above the unit
A
B
A 45° or more
B 300 mm or more
C Front
D 1000 mm or more
E Air outlet guide (Procured at the site)
F Rear
All manuals and user guides at all-guides.com
A
B
C
E
<Side view>
E
D
C
F
When there is little space
up to an obstruction
6.2. Collective installation and continu-
ous installation
Space required for collective installation and continuous installation:
When installing several units, leave the space between each block as
shown below considering passage for air and people.
B
A
C
D
B
C
C
C
F
F
*F
B
A
C
D
B
C
D
D
A
A (Must be open)
B Wall height (H)
C Front
D 1000 mm or more
E 250 mm or more
F 450 mm or more
G 900 mm or more
Note:
•
Open in the two directions.
•
In case wall height (H) exceeds overall height of unit, add "h"
dimension (h=wall height <H> – overall height of unit) to * marked
dimension.
•
If there is a wall at both the front and the rear of the unit, install
up to three units consecutively in the side direction and provide
a space of 1000 mm or more as inlet space/passage space for
each three units.
*E
A
C
B
*F
A
B
C
C
F
F
*E
A
E
C
G
A
E
B
E
A
C
G
7