1. GENERAL INFORMATION
•
This appliance is a sealed electric radiator designed for
fixed wall-mounted installation.
•
This appliance conforms to the standards EN 60 335-1
and EN 60 335-2-30.
•
This appliance is class 2 and splash resistant (IP44).
•
This appliance complies with the European Directive
2004/108/EC (CE Marking on all appliances).
•
This unit is supplied complete with a connection cable,
wall brackets and screws.
2. INSTALLATION
POSITIONING
•
The radiator must be positioned horizontally in order
for it to function correctly.
•
The radiator must be positioned according to the
applicable standards and the minimum distances as
specified in picture 1 should be carefully observed.
•
The radiator may be positioned in volume 2 (picture 2)
of the bathroom, insofar as no operating controls
(button, switch, etc ...) are in reach of persons in the
bath or under the shower.
•
The radiator must be fixed to the wall using the wall
brackets supplied with the radiator and shall not be
located underneath an electrical socket.
FIXING
•
Mark out the distance between the brackets and the
positions for the screw holes as shown in the table in
picture 3a.
•
Insert the safety clips in the wall brackets as shown in
picture 3b.
•
For the correct installation of radiators it is essential that
the fixing of the radiator is carried out in such a way that
it is suitable for intended use AND predictable misuse.
A number of elements need to be taken into
consideration including the fixing method used to
secure the radiator to the wall, the type and condition
of the wall itself, and any additional potential forces or
weights, prior to finalizing installation.
•
The fixing materials provided are only intended for
installation on walls made of solid wood, bricks, concrete
or on timber-frame stud walls where the fixing is into
LVI0014_Manual Ramo_Parada_ZW_v5.indd 21
All manuals and user guides at all-guides.com
the timber. All walls being considered should have no
more than a maximum of 3 mm wall finishing. For walls
made of other materials, for example hollow bricks;
please consult your installer and/or specialist supplier.
In all cases it is strongly recommended that a suitably
qualified professional installer or similar tradesperson
carries out the installation.
CONNECTION
•
The electrical installation must comply with local or
national regulations.
•
The radiator must be connected to the electrical supply
using the supply cable fitted to the unit using a switched
fused spur having 3mm separation on all poles.
•
If the radiator is installed in a bathroom or shower room,
it must be protected with a residual current device (RCD)
with a rated residual current not exceeding 30 mA.
•
The radiator should be connected by a suitable and
qualified electrician. Please refer to the wiring diagram
in picture 4 for the connection of the radiator.
3. OPERATION
•
The On/Off button is located at the bottom of the control
side of the radiator (C, picture 5). The radiator should
only be switched "on" when it is correctly installed
and secured to the wall brackets. When the radiator is
switched "on", the LCD screen will be illuminated and
all segments will be displayed for a few seconds and
disappear. Then the software version will appear shortly
and finally the "Automatic" mode screen will appear.
The backlight will switch off.
•
Display (A, picture 5)
1.
2.
3.
Operating mode menu (active mode is framed)
Parameters number if icon "3" is displayed
Installation parameter menu
GB
GENERAL
INFORMATION
21 |
24-10-13 15:58