SYMBOL (1)
FAULT
Smoke in flame - dark Bacharach
- yellow Bacharach 62 - Too much air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dirty combustion head
During operation, the burner stops
I
in lock out
When the burner does not fire or comes to a halt following a fault, the symbol which appears on control box 24) (Fig. 1 page 7)
(1)
indicates the type of problem.
The fuse is located in the rear part of the control box 24) (Fig. 1 page 7). A pull-out fuse is also available as a spare part which
(2)
can be fitted after breaking the tang on the panel which holds it in place.
5996
All manuals and user guides at all-guides.com
Maintenance
PROBABLE CAUSE
56 - Not enough air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
57 - Nozzle worn or dirty. . . . . . . . . . . . . . . . . . . . . . . . . . . .
58 - Nozzle filter clogged . . . . . . . . . . . . . . . . . . . . . . . . . . .
59 - Erroneous pump pressure . . . . . . . . . . . . . . . . . . . . . . .
60 - Flame stability disk dirty, loose, or deformed . . . . . . . .
61 - Boiler room air vents insufficient . . . . . . . . . . . . . . . . . .
63 - Nozzle or filter dirty . . . . . . . . . . . . . . . . . . . . . . . . . . . .
64 - Unsuitable nozzle delivery or angle. . . . . . . . . . . . . . . .
65 - Loose nozzle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
66 - Impurities on flame stability disk . . . . . . . . . . . . . . . . . .
67 - Erroneous head adjustment or not enough air . . . . . . .
68 - Blast tube length unsuited to boiler . . . . . . . . . . . . . . . .
69 - Dirty or defective photocell . . . . . . . . . . . . . . . . . . . . . .
28
GB
SUGGESTED REMEDY
Adjust head and fan gate
Replace
Clean or replace
Adjust
Clean, tighten in place, or replace
Increase
Adjust head and fan gate
Replace
See recommended nozzles
Tighten
Clean
Adjust, open air damper
Contact boiler manufacturer