WeakAC
Strong distortion of the input voltage can result in the charger hardly operating or
not operating at all. If WeakAC is set, the charger will also accept a strongly
distorted voltage, at the cost of greater distortion of the input current.
Recommendation: Turn WeakAC on if the charger is hardly charging or not
charging at all (which is quite rare!). Also turn on the dynamic current limiter
simultaneously, and reduce the maximum charging current to prevent overloading
the generator if necessary.
Not adjustable with DIP switches.
BoostFactor
Change this setting only after consulting with Victron Energy or with an engineer
trained by Victron Energy!
Not adjustable with DIP switches.
Programmable relay
By default, the multi-functional relay is set as an alarm relay, i.e. the relay will de-
energise in the event of an alarm or a pre-alarm (inverter almost too hot, ripple on
the input almost too high, battery voltage almost too low).
Not adjustable with DIP switches.
Near the connection terminals an LED illuminates when the relay is activated (refer
to S, see appendix A).