5. CONFIGURATION
Settings may only be changed by a qualified engineer
Carefully read the instructions before changes are made.
Batteries should be placed in a dry and well-ventilated area during
charging.
5.1 Standard settings: ready for use
On delivery, the MultiPlus is set to standard factory values. In general, these
settings are suitable for single-unit operation.
Warning: Possibly, the standard battery charging voltage is not suitable for
your batteries. Refer to the manufacturer's documentation, or to your battery
supplier.
Standard MultiPlus factory settings
Inverter frequency
Input frequency range
Input voltage range
Inverter voltage
Stand-alone / parallel / 3-phase
Search mode
Ground relay
Charger on/ off
Battery charge curve
Charge current
Battery type
Automatic equalisation charging
Absorption voltage
Absorption time
Float voltage
Storage voltage
Repeated absorption time
Absorption repeat interval
Bulk protection
AC input current limit
UPS feature
Dynamic current limiter
WeakAC
BoostFactor
Multi-functional relay
PowerAssist
14
50 Hz
45 - 65 Hz
180 - 265 VAC
230 VAC
stand-alone
off
on
on
four-stage adaptive with BatterySafe mode
75 % of the maximum charge current
Victron Gel Deep Discharge (also suitable for
Victron AGM Deep Discharge)
off
14.4 / 28.8 V
up to 8 hours (depending on bulk time)
13.8 / 27.6 V
13.2 / 26.4 V (not adjustable)
1 hour
7 days
on
16 A (= adjustable current limit for
PowerControl and PowerAssist functions)
on
off
off
2
alarm function
on