4.4.5 Parallel Connection
The MultiPlus can be connected in parallel with several identical devices. To this
end, a connection is established between the devices by means of standard RJ45
UTP cables. The system (one or more Multis plus optional control panel) will require
subsequent configuration (see Section 5).
In the event of connecting MultiPlus units in parallel, the following requirements
must be met:
A maximum of six units connected in parallel.
Only identical devices may be connected in parallel.
The DC connection cables to the devices must be of equal length and cross-section.
If a positive and a negative DC distribution point is used, the cross-section of the
connection between the batteries and the DC distribution point must at least equal the
sum of the required cross-sections of the connections between the distribution point and
the MultiPlus units.
Place the MultiPlus units close to each other, but allow at least 10 cm for ventilation
purposes under, above and beside the units.
UTP cables must be connected directly from one unit to the other (and to the remote
panel). Connection/splitter boxes are not permitted.
A battery-temperature sensor need only be connected to one unit in the system. If the
temperature of several batteries is to be measured, you can also connect the sensors of
other MultiPlus units in the system (with a maximum of one sensor per MultiPlus).
Temperature compensation during battery charging responds to the sensor indicating the
highest temperature.
If more than three units are connected in parallel in one system, a dongle is required (see
Section 5).
Only one remote control means (panel or switch) can be connected to the system.
4.4.6 Three-phase operation
The MultiPlus can also be used in 3-phase wye (Y) configuration. To this end,
a connection between the devices is made by means of standard RJ45 UTP cables
(the same as for parallel operation). The system (Multis plus an optional control
panel)
will require subsequently configuration (see Section 5).
Pre-requisites: see Section 4.4.5.
Note: the MultiPlus is not suitable for 3-phase delta (Δ) configuration.