Always disconnect the appliance from the
electricity main before making any adjustments.
All seals must be replaced by the technician at
the end of any adjustments or regulations.
Our burners do not require primary air
adjustment.
9) TAPS
"Reduced rate" adjustment
- Switch on the burner and turn the relative knob to
the "Reduced rate" position (small flame fig. 1).
- Remove knob "M" (fig. 12 and 12/A) of the tap,
which is simply pressed on to its rod. The by-pass
for minimal rate regulation can be: beside the tap
(fig. 12) or inside the shaft. In any case, to access
to regulation, it can be done trought the insertion
of a small screwdriver ''D'' beside the tap (fig. 12)
or in the hole ''C'' inside the shaft of the tap
(fig 12/A). Turn the throttle screw to the right or left
until the burner flame has been adequately
regulated to the "Reduced rate" position.
The flame should not be too low: the lowest small
flame should be continuous and steady. Re-
assemble the several components.
FIG. 12
ADJUSTMENTS
TAPS LUBRIFICATION
Should a tap being blocked, do not
force and ask for Technical
Assistance.
67
It is understood that only burners operating
with G20 or G25 should be subjected to the
above mentioned adjustments. The screw must
be fully locked when the burners operate with
G30 or G31 (turn clockwise).
FIG. 12/A