Decrease the temperature measured by the ambient temperature sensor
by 2°C pressing
. In example, the measured temperature by the
sensor goes from 24°C to 22°C.
2- If the ambient temperature difference is positive, example:
Setting temperature (what you want) = 19°C.
Ambient temperature (what you read on a reliable thermometer) = 21°C.
Difference measured = +2°C.
To correct, then proceed as follows:
Sensor temperature = 21°C (The measured temperature may be different
due to the location of the thermostat in the room).
Increase the temperature measured by the ambient temperature sensor
by 2°C by pressing
. In example, the measured temperature by the
sensor goes from 21°C to 23°C.
To validate the new value press
3 times.
• The reset to zero of the sensor calibration
To put the value of the correction to "0", do the following :
1- When the temperature measured by the sensor appears, press
for at least 3 seconds.
Cod. 1910000000276 - nv01
. To exit the expert settings, press
3 sec.
2- To save and move to the next setting, press
settings, press
3 times
Important: These changes should be performed by a qualified staff, it
should be performed in production or on site during the first installation.
14.3 Setting the power
To have a controller adapted to the towel rails and estimate the energy
consumed, it is essantial to set the power of the device.
1- Pre set value: 500W. Select a value between 500W and 1500W by
pressing
or
2- To save and move to the next setting, press
To exit the Expert settings, press
14.4 Restoring factory settings
If the PIN code is disabled, the user and installer settings are reinitialized:
1- From the PIN code, press
2-
Appears . Press
or
- 35 -
. To exit the installer
.
.
3 times.
.
appears briefly on the display.
or
to select
.
English