- Loadshedding X: If a 'loadshedding' switch is integrated in a system (see fig.), Vout max. X
cannot rise above the set value if the switch is switched on.
Adjustable between: 0 – 10V; standard 5V.
Application: close the 'loadshedding' switch in order to save energy at specific moments, so
the lighting is only switched on at a lower level of daylight.
Adjust Settings:
- Copy settings:
1)Custom to Backup: the settings in custom mode are copied to backup mode
2) Backup to Custom: the settings in backup mode are copied to custom mode, so making
changes is possible.
3) Factory to Custom: the factory settings are loaded in custom mode.
4) Factory to Backup: the factory settings are loaded in backup mode.
You are recommended to always make a backup of the settings. After you have done this, preferably
work in backup mode (see '5.1. GENERAL SET').
- Initiate sensor:
If the system is started without the light sensor is connected or if you have the impression that the
light sensor measures wrong values, you can best initiate the sensor once again.
5.3. Status (see 'Quickguide', D)
In this menu, you can view the status of a number of system parameters.
Ch1 .............. channel 1
Ch2 .............. channel 2
Ch3 .............. channel 3
Vout X: current output voltage for channel X (1-10V control)
Df1 ............... daylight factor 1; relation between Lx ind1 and sensor
Df2 ............... daylight factor 2; relation between Lx ind2 and sensor
Df3 ............... daylight factor 3; relation between Lx ind3 and sensor