- Range (bereik): standard 30-30klx
- Lx ind X: Insert the daylight level you measure by a lux meter in the different zones (1, 2, 3).
Preferably measure the daylight level at table height.
- Sensor: Insert the daylight level the sensor (placed by the window) measures. The displayed
sensor value is a snapshot of the actual sensor value at the moment you opened this sub
menu.
Adjust CH X:
In these 3 sub menus, you can set the parameters per channel (CH).
- Setp X: Setpoint. This is the min. light level that is actually required in a zone zone (1, 2, 3).
If there is sufficient daylight, the lighting is switched on and is dimmed to the desired light
level (setp).
- Vout min X: adjustable between 0 – 4V; standard 0V
- Vout max X: adjustable between 6 – 10V; standard 10V
- Fade up X: adjustable between 5 – 60s; standard 10s
- Fade down X: adjustable between 5 – 60s; standard 10s
- Off delay: only adjustable below CH1, but functions identically for all active channels (max.
3 channels).
After the last detected movement, the system counts down the 'off delay'. If the set time elapses
before a new movement is detected, the light level is dimmed to Vout in all active channels.
In case of motion detection before the 'off delay' has elapsed, the light level is automatically
adjusted in all active channels (zones).
Adjustable between 1 – 60min; standard 10min.
- Cut off X: The 'cut off' is typical for channel X.
If the 'off delay' has elapsed and the active channels are dimmed to Vout min., the 'cut off
delay' starts counting down. If no movement is detected and the 'cut off delay' elapses, the
load (lighting) for this channel is switched off.
Adjustable between: 0min – unlimited. Standard 8min.