Wiring diagram (fig.2)
- Connect the light sensor (350-10011) and motion sensor (350-20010/350-20011) to terminal
range A. You can connect several motion sensors (max. 8) in parallel. You can only connect one
light sensor per system.
- Connect the manual controls to terminal range B.
- 1-10V outputs (terminal range D)
- Connect the RJ12-inputs of the Power Pack and the daylight control module via 390-40011.
Startup
The light sensor (350-10011) has to be placed and connected correctly before switching on the
power supply. Proceed as follows:
- Switch on the power supply.
- Accept the displayed sensor value.
- The module is powering up.
- The module is ready for use.
If the daylight control module has been powered up before the light sensor was connected correctly,
you can repeat the initiation (see 5.2. ADJUSTMENT -> Adjust settings).
4. OPERATION AND USE
4.1 Light sensor (350-10011) (fig.2)
The lighting is switched on if the sensor measured insufficient daylight.
4.2 Motion sensor (350-20010/350-20011) (fig.2)
The motion sensor(s), max. 8 in parallel, enable the lighting to be switched on in case motion
is detected.