8.5.2
n
EN
8.5.3
42
Mains power
Note
The water heater is supplied without a power cable and isolator.
Use a power cable with wires of a suitable diameter based on the cable length and the
current.
Note
Select and install an overvoltage category III, all–pole isolator with a contact gap of at
least 3 mm. The all–pole isolator must be incorporated in the fixed wiring in accordance
with the wiring rules.
Note
This isolator must be installed in the same room as the appliance, suitably marked and
no more than 1 meter away from the water heater.
Note
The length of the mains earth core that is connected to the electrical connection must be
longer than the core of the mains live (L1, L2 and L3).
Connect the water heater to the mains power supply:
1.
Pull the power cable through the cable gland.
2.
Connect the live (L1, L2 and L3) and the earth (A) core of the power cable to the
terminals of the terminal block.
3.
Connect the power cable to the isolator.
4.
Secure the power cable in the cable gland.
Alarm output
The alarm output allows you to transmit the alarm status to an external device. The alarm
output is a relay.
Normally Open (NO)
Normally Closed (NC)
COM
NC NO
X1
11
21
22 24 12 14
A2
A1
Connections
Supply
Output
11
14
21
24
11
12
21
22