Device informa-
For displaying the settings that will be of relevance to a power supply company.
tion
The values shown will depend on the country setup or the device-specific set-
tings of the inverter.
General:
Country-specific
setting:
MPP Tracker:
Grid monitoring:
Grid voltage limits
inner limit value:
Grid voltage limits
outer limit value
Grid frequency lim-
its:
Q-mode:
AC power limit in-
cluding SoftStart in-
dicator and/or AC
grid frequency de-
rating:
40
Device type - the exact name of the inverter
fam. - inverter family of the inverter
serial number - serial number of the inverter
Setup - specified country setup
Version - version of country setup
Origin activated - indicates that the normal country-specific setup is activ-
ated.
Group - group for updating the inverter software
Tracker 1 - indicates the set tracking behaviour (MPP AUTO / MPP USER /
FIX)
Tracker 2 (only on Fronius Symo except for Fronius Symo 15.0-3 208) - in-
dicates the set tracking behaviour (MPP AUTO / MPP USER / FIX)
GMTi - Grid Monitoring Time - start-up time of the inverter in sec (seconds)
GMTr - Grid Monitoring Time reconnect - reconnection time in sec (seconds)
after a grid fault
ULL - U (voltage) Longtime Limit - voltage limit value in V (volts) for the 10-
minute average voltage value
LLTrip - Longtime Limit Trip - trip time for ULL monitoring, how fast the in-
verter should switch off
UImax - upper inner grid voltage in V (volts)
TTMax - Trip Time Max - trip time for exceeding the upper inner grid voltage
limit value in cyl*
UMin - lower inner grid voltage in V (volts)
TTMin - Trip Time Min - trip time for falling below the lower inner grid
voltage limit value in cyl*
UMax - upper outer grid voltage in V (volts)
TTMax - Trip Time Max - trip time for exceeding the upper outer grid voltage
limit value in cyl*
UMin - lower outer grid voltage in V (volts)
TTMin - Trip Time Min - trip time for falling below the lower outer grid
voltage limit value in cyl*
FILmax - upper inner grid frequency in Hz (Hertz)
FILmin - lower inner grid frequency in Hz (Hertz)
FOLmax - upper outer grid frequency in Hz (Hertz)
FOLmin - lower outer grid frequency in Hz (Hertz)
Indicates which reactive power setting is currently active on the inverter (e.g.
OFF, Q / P, etc.)
Max P AC - maximum output power, which can be changed using the "Manu-
al Power Reduction" function
GPIS - Gradual Power Incrementation at Startup - indicates (%/sec) wheth-
er the SoftStart function is active on the inverter
GFDPRe - Grid Frequency Dependent Power Reduction enable limit - indic-
ates the set grid frequency in Hz (Hertz) from when power derating takes
place
GFDPRv - Grid Frequency Dependent Power Reduction derating gradient -
indicates the set grid frequency in %/Hz, how strong power derating is