Shut off the air supply
2.
Notify the fire department
3.
Enable acces to the cleaning hatch (e.g. in the cellar or attic)
4.
Remove all combustible objects away from the chimney
5.
Always have the chimney and stove checked by an expert before using the stove again.
6.
The expert needs to check what caused the chimney fire and how to prevent it.

5. Combustion air

The Saey ePure wood-burning stove can only be used when the door of the stove is closed. The Saey
ePure wood-burning stove consumes 28m³ of air at its nominal capacity. The combustion air is preferably
taken from outside by means of an airbox (available as an option).
Other fireplaces or air outlets in the same space or with the same combustion air connection, must be taken
into account.
If necessary, the combustion air connection must be calculated, or a separate combustion air supply must
be installed outside.
Tip: cooker hoods that could be connected to the space in which the stove is set up, must certainly be
taken into account. They cause an under pressure that could lead to disturbances in the combustion air
supply. The combustion gas that is released is highly dangerous and could be harmful to the health of the
house occupants.

Combustion air inlet: conventional

5.1
The Saey ePure wood-burning stove obtains its combustion air solely via the air slider (air inlet) on the
back of the stove on the bottom.

Combustion air inlet: separate / external

5.2
In order to guarantee a healthy environment / air in the room, it is strongly advisable to take the
combustion air from outside, this by means of the airbox (available as an option). From the airbox, you
continue with a tube with Ø 100 mm.
If a smooth pipe with a diameter of 100 mm is used, 12 m of pipe can be connected. If adapters such as
elbow joints are used, the maximum length of the pipes should be decreased by 1 m per adapter. E.g.
10m of pipe + 2 elbow joints = 12 m of pipe.

Assembly of the airbox

5.3
1. first, the protection plate at the back of the stove should be removed (4 screws).
2. take the cotter pin out of the pivot of the airslider
3. unscrew the fixing screw from the air slider and defuse
4. unscrew the pivot of the air slider
5. move the air slider to the right (minimum / no supply of combustion air)