COF Compressor OFF time with faulty
probe
CF
Temperature measurement unit
rES Resolution
Lod Probe displayed
2
rEd
X-REP display
dLy Display temperature delay
dtr
P1-P2 percentage for disply
tdF Defrost type
dFP Probe selection for defrost termination
dtE Defrost termination temperature
IdF Interval between defrost cycles
MdF (Maximum) length for defrost
dSd Start defrost delay
dFd Displaying during defrost
dAd MAX display delay after defrost
Fdt Draining time
dPo
First defrost after startup
dAF Defrost delay after fast freezing
Fnc Fan operating mode
Fnd Fan delay after defrost
Fct Differential of temperature for forced
activation of fans
FSt Fan stop temperature
Fon Fan on time with compressor off
FoF Fan off time with compressor off
FAP Probe selection for fan management
ALc Temperat. alarms configuration
ALU MAXIMUM temperature alarm
ALL Minimum temperature alarm
AFH Differential for temperat. alarm
recovery
ALd Temperature alarm delay
dAO Delay of temperature alarm at start up
AP2 Probe for temperat. alarm of
condenser
AL2 Condenser for low temperat. alarm
AU2 Condenser for high temperat. alarm
Differ. for condenser temp. alar.
AH2
recovery
Ad2 Condenser temperature alarm delay
Delay of cond. temper. alarm at start
dA2
up
Compr.
off
for
condenser
bLL
temperature alarm
Compr. off for
condenser
AC2
temperature alarm
tbA Reset alarm relais
oA3 Configuration of alarm relais
AoP Alarm relais polarity
i1P Digital input polarity
i1F Digital input configuration
did Digital input alarm delay
Nps Number of activation of pressure
switch
odc Compress and fan status with open
door
rrd
Regulation restart with door open
alarm
HES Differential for Energy Saving
PbC Kind of probe
Adr Serrial address
onF on/off key enabling
dP1 Room probe display
dP2 Evaporator probe display
dP3 Third probe display
dP4 Fourth probe display
rSE Valore set operativo
rEL Software release
Ptb Map code
2
enkel voor de modellen XR70CX–xx2xx, XR70CX–xx3xx;
XR70CX
Installatie en gebruikershandleiding
0 ÷ 255 min
°C ÷ °F
in=integer; dE= dec.point
P1;P2
P1 - P2 - P3 - P4 - SEt - dtr
0 ÷ 20.0 min (10 sec.)
1 ÷ 99
EL=el. heater; in= hot gas
nP; P1; P2; P3; P4
-50 ÷ 50 °C
1 ÷ 120 ore
0 ÷ 255 min
0÷99min
rt, it, SEt, DEF
0 ÷ 255 min
0÷120 min
n=after IdF; y=immed.
0 ÷ 23h e 50'
C-n, o-n, C-y, o-Y
0÷255min
0÷50°C
-50÷50°C/-58÷122°F
0÷15 (min.)
0÷15 (min.)
nP; P1; P2; P3; P4
rE= related to set; Ab = absolute
Set÷110.0°C; Set÷230°F
-50.0°C÷Set/ -58°F÷Set
-50.0
(0,1°C÷25,5°C) (1°F÷45°F)
0 ÷ 255 min
0 ÷ 23h e 50'
nP; P1; P2; P3; P4
(-55 ÷ 150°C) (-67÷ 302°F)
(-55 ÷ 150°C) (-67÷ 302°F)
[0,1°C ÷ 25,5°C] [1°F ÷ 45°F]
0 ÷ 254 (min.) , 255=nU
0.0 ÷ 23h 50'
low
n(0) - Y(1)
high
n(0) - Y(1)
n=no; y=yes
ALr = alarm; dEF =do not
use; Lig =light;
AUS =AUX; onF=always
on; Fan= do not use; db =
do not use ; dF2 = do not
use
oP=opening;CL=closing
oP=opening;CL=closing
EAL, bAL, PAL, dor; dEF; Htr, AUS
0÷255min
0 ÷15
no; Fan; CPr; F_C
n – Y
(-30°C÷30°C) (-54°F÷54°F)
Ptc; ntc
1÷247
nu, oFF; ES
--
--
--
--
actual set
--
--
30
Pr2
°C
Pr2
dE
Pr1
P1
Pr2
P1
Pr2
0
Pr2
50
Pr2
EL
Pr1
P2
Pr2
8
Pr1
6
Pr1
30
Pr1
0
Pr2
it
Pr2
30
Pr2
0
Pr2
n
Pr2
0.0
Pr2
o-n
Pr1
10
Pr1
10
Pr2
2
Pr1
0
Pr2
0
Pr2
P2
Pr2
Ab
Pr2
110
Pr1
Pr1
1
Pr2
15
Pr2
1.3
Pr2
P4
Pr2
-40
Pr2
110
Pr2
5
Pr2
15
Pr2
1,3
Pr2
n
Pr2
n
Pr2
y
Pr2
Alr
Pr2
cL
Pr2
cL
Pr1
dor
Pr1
15
Pr1
15
Pr2
F-c
Pr2
y
Pr2
0
Pr2
1
Pr2
1
Pr2
ntc
Pr1
nu
Pr2
--
Pr1
--
Pr1
--
Pr1
--
Pr2
--
Pr2
--
Pr2