Deze parameter kan niet worden geselecteerd
via de seriële poort, RS 485.
NB!:
Als de [OK]-toets ingedrukt is, heeft de
reset plaatsgevonden.
620 Operating mode
(OPERATION MODE)
Waarde:
Normal function (NORMAL OPERATION)
Function with de-acti v ated inverter
(OPER. W/INVERT.DISAB)
Control card test (CONTROL CARD TEST)
Initialisation (INITIALIZE)
Functie:
In addition to its normal function, this parameter
can be used for two different tests.
Furthermore, it is possible to reset to the default
factory settings for all Setups, except parameters
500 Address, 501 Baud rate, 600-605 Operating
data and 615-617 Fault log.
Beschrijving van de keuze:
Normal function [0] is used for normal
operation of the motor.
Function with de-acti v ated inverter [1] is selected if
control is desired over the influence of the control
sig-nal on the control card and its functions -
without the motor shaft running.
Control card [2] is selected if control of the analogue
and digital inputs, analogue and digital outputs, relay
outputs and the control voltage of +10 V is desired.
A test connector with internal connections
is required for this test.
The test connector for the Control card [2]
is set up as follows:
connect
4-16-17-18-19-27-29-32-33;
connect
5-12;
connect
39-20-55;
connect
42 - 60;
connect
45-53-54.
= standaardinstelling. () = display-tekst [] = waarde gebruikt voor communicatie via seriële communicatiepoort.
134
®
VLT
Serie 6000 HVAC
[0]
Use the following procedure for the control card test:
[1]
1. Select Control card test.
[2]
2. Cut off the mains supply and wait for the
[3]
light in the display to go out.
3. Insert the test plug (see preceding column).
4. Connect to mains.
5. The frequency converter expects the [OK] key to be
pressed (the test cannot be run without LCP).
6. The frequency converter automatically
tests the control card.
7. Remove the test connector and press the
[OK] key when the frequency converter
displays "TEST COMPLETED".
8. Parameter 620 Operating mode is automatically
set to Normal function.
If the control card test fails, the frequency conver-ter
will display "TEST FAILED". Replace the control card.
Initialisation [3] is selected if the factory setting
of the unit is to be generated without resetting
parameters 500 Address, 501 Baud rate, 600-605
Operating data and 615-6171 Fault log.
Procedure for initialisation:
1. Select Initialisation.
2. Press the [OK] key.
3. Cut off the mains supply and wait for the
light in the display to go out.
4. Connect to mains.
5. Initialisation of all parameters will be carried out
in all Setups with the exception of parameters
500 Address, 501 Baud rate, 600-605 Operating
data and 615-617 Fault log.
Manual initialisation is another option. (See
Manual initialisation).