10.1. Power supply wiring
•
Power supply cords of appliances shall not be lighter than design 245 IEC 57
or 227 IEC 57.
•
A switch with at least 3 mm contact separation in each pole shall be provided
by the Air conditioner installation.
ELECTRICAL WORK
1. Electrical characteristics
Model
Hz
50/60
PWFY-P100VM-E-BU
Model
PWFY-P100VM-E-AU
50/60
PWFY-P200VM-E-AU
2. Power cable specifications
Minimum wire thickness (mm
Model
Main cable
2.5
PWFY-P100VM-E-BU
Model
Total
16 A or less
PWFY-P100VM-E-AU
operating
25 A or less
PWFY-P200VM-E-AU
current
32 A or less
[Fig. 10.1.1] (P. 4)
A Breaker for current leakage
B Local switch or breakers for wiring
C PWFY-P100VM-E-BU
D PWFY-P100/200VM-E-AU
E Pull box
Caution:
Do not use anything other than the correct capacity breaker and fuse. Us-
ing fuse, wire or copper wire with too large capacity may cause a risk of
malfunction or fire.
10.2. Connecting remote controller, indoor
and outdoor transmission cables
(Remote contoroller is optionally available.)
•
Connect unit TB5 and outdoor unit TB3. (Non-polarized 2-wire (shield))
The "S" on unit TB5 is a shielding wire connection. For specifications about
the connecting cables, refer to the outdoor unit installation manual.
•
Install a remote controller following the manual supplied with the remote con-
troller.
•
Connect the "1" and "2" on unit TB15 to a MA remote controller. (Non-polar-
ized 2-wire)
[Fig. 10.2.1] (P.4) MA Remote controller
•
DC 10 to 13 V between 1 and 2 (MA remote controller)
[Fig. 10.2.2] (P.4) MA Remote controller
•
The MA remote controller cannot be used at the same time or interchange-
ably.
A Non-polarized
C MA remote Controller
E TB2 (Power supply wiring)
Note:
Ensure that the wiring is not pinched when fitting the terminal box cover.
Pinching the wiring may cut it.
Caution:
•
Use wire with supplemental insulation.
•
Input to TB142A, TB142B, and TB142C should not carry voltage.
•
Cables from equipment connected to external input/output should have sup-
plemental insulation.
•
Use a single multiple-core cable for external input/output to allow for connec-
tion to the PG screw.
Caution:
Wire the power supply so that no tension is imparted. Otherwise discon-
nection, heating or fire result.
All manuals and user guides at all-guides.com
Power supply
Volts
Voltage range
Max. 264 V
220-230-240 V
Min. 198 V
Power supply
Hz
Volts
220-230-240 V
2
Breaker for
)
current leakage
branch
Ground
30 A 30 mA 0.1 sec or less
2.5
-
2
Minimum wire thickness (mm
)
Main cable
branch
Ground
1.5
1.5
1.5
2.5
2.5
2.5
4.0
4.0
4.0
B TB15 (MA remote controller cables)
D TB5 (Transmission cables)
Compressor
MCA (A)
Output (kW)
SC (A)
15.71
1.0
Voltage range
MCA (A)
Max. 264 V
0.085
Min. 198 V
Local swich (A)
capacity
fuse
25
25
Breaker for
Local swich (A)
current leakage
capacity
16
20 A 30 mA 0.1 sec. or less
25
30 A 30 mA 0.1 sec. or less
32
40 A 30 mA 0.1 sec. or less
10.3. External input/output function
Preset temperature input (external analog input: 4mA-20mA)
External input is input through CN421, CN422 on the circuit board. (Fig. 10.3.1)
Use the supplied connector.
If no temperature settings are made via the MA remote controller, the temperature
changes with the current.
Refer to the instructions manual that came with the MA remote controller for how
to make the settings.
4 mA → 10 °C
20 mA → 70 °C
External output terminal
External output terminal (refer to Fig. 10.3.2) is ineffective when the circuit is open.
Refer to Table 10.3.2 for information about each contact.
The current in the circuit to be connected to the external output terminal must be
0.6A or less.
Table10.3.2
OUT1
Operation ON/OFF
OUT2
Defrost
OUT3
Compressor
Error signal
OUT4
External input terminal
The piping length must be within 100 m.
External input terminal (refer to Fig. 10.3.3) is ineffective when the circuit is open.
Refer to Table 10.3.3 through Table 10.3.5 for information about each contact.
Only the "pump interlock" function is ineffective when the circuit is short-circuited.
Connect a relay circuit to the external output terminal as shown in Fig. 7.4.1.
The specifications of the relay circuit to be connected must meet the following
conditions.
Contact rating voltage
DC15V
=
Contact rating current
0.1A
=
Minimum applicable load
1mA at DC
=
Table10.3.3
TB142A
IN1
Pump interlock
Table10.3.4
TB142B
IN3
Connection demand
IN4
Operation ON/OFF
Table10.3.5
TB142C
COM+
Common
IN5*1
Hot Water/Heating
Heating ECO
IN6*2
Anti-freeze
IN7*3
*1 PWFY-P100VM-E-BU
PWFY-P100/200VM-E-AU
*2 Effective when SW 4-3 is set to ON.
*3 Effective when SW 4-4 is set to ON.
RLA (A)
Heating
1.25
11.63-11.12-10.66
RLA (A)
Cooling
Heating
0.068-0.065-0.063
Breaker for wiring (NFB) (A)
30
Breaker for wiring (NFB) (A)
fuse
16
20
25
30
32
40
Hot Water
Heating
11