DANSK
1. Montering af AME 20, AME 30 på
ventil (fig.5)
Fastgør AME 20, AME 30 på
ventilen.
2. Indstilling af funktionsomskifter
(fig. 9)
Løsn skruen i låget. Fjern låget. På
printet er der tre lus til rådighed til
valg af specialindstillinger (fig. 9).
Fig. 9.2 (Y = 2 -10 V, fabriksindstilling)
Motorspindlen i AME 20, AME 30
bevæger sig nedad i takt med, at
styrespændingen stiger.
Fig 9.3 (Y = 0 - 10 V)
Motorspindlen i AME 20, AME 30
bevæger sig nedad i takt med, at
styrespændingen stiger.
Fig. 9.4 (Y = 4 - 20 mA)
Motorspindlen i AME 20, AME 30
bevæger sig nedad i takt med, at
styrestrømmen stiger.
Fig. 9.5 (Y = 0 - 20 mA)
Motorspindlen i AME 20, AME 30
bevæger sig nedad i takt med, at
styrestrømmen stiger.
Fig. 9.6 (Y = 10 - 2 V)
Motorspindlen i AME 20, AME 30
bevæger sig opad i takt med, at
styrespændingen stiger.
Fig. 9.7 (Y = 10 - 0 V)
Motorspindlen i AME 20, AME 30
bevæger sig opad i takt med, at
styrespændingen stiger.
Fig. 9.8 (Y = 20 - 4 mA)
Motorspindlen i AME 20, AME 30
bevæger sig opad i takt med, at
styrestrømmen stiger.
Fig. 9.9 (Y = 20 - 0 mA)
Motorspindlen i AME 20, AME 30
bevæger sig opad i takt med, at
styrestrømmen stiger.
Bemærk: Lusene kan indstilles før og
efter selvjustering.
3. El-tilslutning (fig. 7)
3.1 Styresignal
Styresignal fra regulatoren skal til-
sluttes klemme Y (indgangssignal) og
klemme SN (fælles) på AME-printet.
3.2 Udgangssignal
Udgangssignalet fra klemme X kan
anvendes til at indikere den aktuelle
position. Området afhænger af lusen
2/0 (2 - 10 V eller 0 - 10 V).
3.3 Forsyningsspænding
Forsyningsspændingen (24 V~,
-15/+10 %, 50 Hz) skal tilsluttes
klemme SN og SP.
7369222-9 SIBC R&D
4. Drift
Efter at der er sluttet strøm til
aktuatoren, starter denne en
selvjusteringsproces. Lysdioden
blinker, indtil selvjusteringen er
afsluttet. Varighed normalt et par
minutter, afhængig af
spindelvandringen. Ventilens
slaglængde gemmes i hukom-
melsen efter afsluttet selvjustering.
Et tryk på RESET-tasten (fig. 9) vil
genstarte selv-justeringen. Hvis
forsyningsspændingen er afbrudt -
eller falder til under 80% - i mere end
0,1 s, gemmes den aktuelle
ventilposition i hukommelsen. Alle
data vil således være sikret i
hukommelsen - også i tilfælde af
strømafbrydelse.
5. Funktionstest
Lysdioden indikerer, om motoren er i
drift, ligesom den viser driftsstatus og
eventuelle fejl.
Konstant lys
- normal drift
Intet lys
- ikke i drift, ingen strømforsyning
Intervalblink (1 Hz)
- selvjusteringsmodus
Intervalblink (3 Hz)
- strømforsyning for lav
- ventilslaglængde utilstrækkelig
AME 20 <20 s
AME 30 <12 s
- endestilling kan ikke nås.
ENGLISH
1. Mounting the AME 20, AME 30 on a
valve (Fig. 5).
Fix the AME 20, AME 30 on the
valve.
2. Function switch setting (Fig. 9)
Unscrew the screw on the top of the
lid. Remove the lid. On the printed
board three jumpers are available for
selecting special settings (Fig. 9).
Fig. 9.2 (Y = 2 - 10V, factory setting)
The AME 20, AME 30 motor spindle
travels downwards on rising control
voltage.
Fig. 9.3 (Y = 0 - 10V )
The AME 20, AME 30 motor spindle
travels downwards on rising control
voltage.
Fig. 9.4 (Y = 4 - 20mA)
The AME 20, AME 30 motor spindle
travels downwards on rising control
current.
Fig. 9.5 (Y = 0 - 20mA)
The AME 20, AME 30 motor spindle
travels downwards on rising control
current.
Fig. 9.6 (Y = 10 - 2V)
The AME 20, AME 30 motor spindle
travels upwards on rising control
voltage.
EI.96.U1.5Q © Danfoss 9/98
Fig.9.7 (Y = 10 – 0V)
The AME 20, AME 30 motor spindle
travels upwards on rising control
voltage.
Fig.9.8 (Y = 20 – 4mA)
The AME 20, AME 30 motor spindle
travels upwards on rising control
current.
Fig.9.9 (Y = 20 – 0mA)
The AME 20, AME 30 motor spindle
travels upwards on rising control
current.
Note: Jumpers can be set before or after
self-adjustment.
3. Wiring (Fig.7)
3.1 Control signal
Control signal from the controller
must be connected to terminals Y
(input signal) and SN (common) on
the AME printed board.
3.2 Output signal
Output signal from the terminal X can
be used for indication of the current
position. Range depends on the
jumper 2/0 (2 – 10V or 0 – 10V).
3.3 Supply voltage
Supply voltage (24V~ -15 to +10%,
50Hz) must be connected to the
terminals SN and SP.
4. Operation
After the actuator has been connected
with power supply, the actuator will
start the self-adjustment procedure.
The indicator LED flashes until self-
adjustment is finished. The duration
depends on the valve spindle travel
and actuator speed. The stroke
lenght of the valve is stored in the
memory after self-adjustment has
been completed.
To restart self-adjustment, press RE-
SET key (Fig.9). If the supply voltage
is switched off or falls below 80% in
more than 0.1s, the current valve posi-
tion will be stored in the memory and
all data remain saved in the memory
also after a power supply cut-out.
5. Function test
The indicator light shows whether the
positioner is in operation or not.
Moreover, the indicator shows the
control status and faults.
Constant light
- normal operation
No light
- no operation or no power supply
Interval light (1 Hz)
- self adjusting-mode
Interval light (3 Hz):
- power supply too low
- insufficient valve stroke
AME 20 <20 s
AME 30 <12 s
- end-position cannot be reached.