english
Inline EBZ-E with integrated frequency converter
Configuration
Details of EBZ-E order
Object:
Street:
Place:
Person resp.:
Pump EBZ-E:
Special:
Configuration:
Regulated with pump-internal PI-regulator
1
The pump regulates itself
Setting adjustment, binding post 4-6
A
with control keys
C
with external set point-signal 0 .. 10 V
D
with external set point-signal 0 .. 20 mA
E
with external set point-signal 4 .. 20 mA
Instantaneous value measurement, binding post 7-8
differential pressure transmitter fitted 4 .. 20 mA
F
H
with external actual value signal from 0 .. 10 V
I
with external actual value signal from 0 .. 20 mA
K
with external actual value signal from 4 .. 20 mA
Regulated with pump-internal PI-controller
L
proportional direct (pls. refer to pump diagram)
M
constant direct (pls. refer to pump diagram
Regulated with external controller
2
(Control keys on pump are inactive)
The client must have control possibility
e.g. SPS-control with analogue On/Off exit (output?)
Heating - air-conditioning control with analogue On/Off exit, etc.
Set-point adjustment, binding post 4-6
P
with external set point-signal 0 .. 10 V
Q
with external set point-signal 0 .. 20 mA
R
with external set point-signal 4 .. 20 mA
Function digital entry, binding post 1+3
U
Minimum speed (e.g. reduction during the night)
V
Maximum speed
W
alarm reset
(potential-free reset button integrated in the building)
Note:
For each pump programmed before delivery,
the delivery time starts the day
this configuration sheet is received.
Change of configuration must only be performed
by Biral service technician.
56
All manuals and user guides at all-guides.com
Purchaser:
Address:
Place:
Techn. person in charge:
Phone:
Biral order number:
Flow (m
Head (kPa/m):
Head set-point in (kPa/m):
Pushbuttonposition
without change of configuration
Setting when supplied 1, A, F, L, U, X
Function digital entry, binding post 1+3
U
Minimum speed (e.g. reduction during the night)
V
Maximum speed
W
alarm reset
(potential-free reset button integrated in the building)
Function relays contact, C-NO-NC
Opener: C-NC, Closer: C-NO
fault message: contact closes,
X
if pump has voltage and obstruction present
Ready: contact closes,
Y
if pump has voltage and no obstruction present
Operation: contact closes, if pump is running
Z
alarm reset by opening of start contacts,
binding post 2-3
stop + alarm if set-point error
stop + alarm if sensor error (only if 20 mA signal)
Only one setting possible per field
without change of configuration
Setting when supplied 2, P, U, X
Function relay contact, C-NO-NC
Opener: C-NC, Closer: C-NO
Fault message: contact closes,
if pump has voltage
X
Ready: contact closes,
if pump has voltage and no obstruction present
Y
Operation: contact closes, if motor rotates
alarm reset by opening of start contacts,
Z
binding post 2-3
Only one setting possible per field
Place:
Date:
Signature:
3
/h):