Logic
Definition
Step-by-step
STEP-BY-STEP
movement
MOVEMNT
Encoder
Encoder
Pre-alarm
PRE-ALARM
Deadman
HOLD-TO-RUN
Block pulses du-
IBL OPEN
ring opening
Block pulses
|IBL TCA
during TCA
Block pulses
IBL CLOSE
during closing
Open in other
OPEN IN OTHER
direction
DIRECT.
Configuration
of safety input
SAFE 1
SAFE 1.
Configuration
of safety input
SAFE 2
SAFE 2.
Configuration
of safety input
SAFE 3
SAFE 3.
38 -
LEO B CBB DL2 3 230 L02-LEO B CBB DL2 3 120
INSTALLATION MANUAL
Cross out
Default
setting
used
0
2
LEO B CBB DL2 3
120 F02
(only for sw ver-
sions 7.08)
LEO B CBB DL2 3 120
F02 PHOT USA16
(only for sw ver-
sions 8.08)
0
0
0
0
0
0
0
72
6
74
2
77
F02-LEO B CBB DL2 3 120 F02 PHOT USA16
Inputs configured as Start E, Start I,
0
Ped operate with 4-step logic.
Inputs configured as Start E, Start I,
1
Ped operate with 3-step logic. Pulse
during closing reverses movement.
Inputs configured as Start E, Start
2
I, Ped operate with 2-step logic.
Movement reverses with each pulse.
Operation with encoder disabled
WARNING
This setting fully disables the anti-crush safety
device, with serious safety risks.
0
Install active safety edges on closing and opening or
switch to deadman operation. (see Deadman logic)
The slowing down spaces are an estimate made
through the gate travel time.
For greater precision on the slowing down point,
set encoder = 1 or 2.
Operation with encoder used as position sensor for
acquiring slow-down distances. - Gate detection
1
locked out. Manual setting of "opening force", "clo-
sing force", "opening slow-down force" and "closing
slow-down force" parameters.
2
Automatic mode with encoder: slow-down and
obstacle detection performed by means of enco-
der. Adjustment of obstacle detection sensitivity
(opening force, closing force, opening slow-down
force, closing slow-down force parameters) (de-
fault setting).
0
The flashing light comes on at the same time as the motor(s) start.
1
The flashing light comes on approx. 3 seconds before the motor(s) start.
0
Pulse operation.
Deadman mode.
Input 61 is configured as OPEN UP.
Input 62 is configured as CLOSE UP.
1
Operation continues as long as the OPEN UP or CLOSE UP keys are held down.
WARNING: safety devices are not enabled.
Emergency Deadman mode. Usually pulse operation.
If the board fails the safety device tests (photocell or safety edge, Er0x) 3 times in a row, Deadman mode is
enabled which will stay active for 1 minute after the OPEN UP - CLOSE UP keys are released.
Input 61 is configured as OPEN UP.
2
Input 62 is configured as CLOSE UP.
WARNING: with the device set to Emergency Deadman mode, safety devices are not enabled.
0
Pulse from inputs configured as Start E, Start I, Ped has effect during opening.
1
Pulse from inputs configured as Start E, Start I, Ped has no effect during opening.
0
Pulse from inputs configured as Start E, Start I, Ped has effect during TCA pause.
1
Pulse from inputs configured as Start E, Start I, Ped has no effect during TCA pause.
0
Pulse from inputs configured as Start E, Start I, Ped has effect during closing.
1
Pulse from inputs configured as Start E, Start I, Ped has no effect during closing.
0
Standard operating mode (Fig.G Rif. 1).
1
Opens in other direction to standard operating mode (Fig. G Rif.2)
0
Input configured as Phot (photocell).
1
Input configured as Phot test (tested photocell).
2
Input configured as Phot op (photocell active during opening only).
3
Input configured as Phot op test (tested photocell active during opening only).
4
Input configured as Phot cl (photocell active during closing only).
5
Input configured as Phot cl test (tested photocell active during closing only).
6
Input configured as Bar, safety edge.
7
Input configured as Bar, tested safety edge.
Input configured as Bar 8k2 (Inactive on SAFE 3).
8
9*
Input configured as Bar OP, safety edge with inversion active only while opening. If while closing, the movement stops.
Input configured as Bar OP TEST, safety edge tested with inversion active only while opening. If while closing,
10*
the movement stops.
Input configured as Bar OP 8k2, safety edge with inversion active only while opening. If while closing, the
11*
movement stops.
(Inactive on SAFE 3).
12*
Input configured as Bar CL, safety edge with inversion active only while closing. If while opening, the movement stops.
Input configured as Bar CL TEST, safety edge tested with inversion active only while closing. If while opening,
13*
the movement stops.
Input configured as Bar CL 8k2, safety edge with inversion active only while closing. If while opening, the
14*
movement stops.
(Inactive on SAFE 3).
Optional extras
step-by-step mov.
2 STEP
3 STEP
CLOSED
OPENS
OPENS
DURING
CLOSING
OPEN
CLOSES
CLOSES
DURING
STOP + TCA STOP + TCA
OPENING
AFTER STOP
OPENS
OPENS
WARNING: Check that the force of impact measured at
the points provided for by standard EN 12445 is lower
than the value laid down by standard EN 12453.
WARNING: Setting sensitivity incorrectly can
result in damage to property and injury to people
and animals.
4 STEP
OPENS
STOPS
CLOSES
OPENS