Function
Description
Code no.
9-09
Motor Type Selection
Motor Overload
9-10
Protection Curve
Selection
Operation After
9-11
Overload Protection
is Activated
Over torque
9-12
Detection Selection
Operation After Over
9-13
torque Detection is
Activated
Over torque
9-14
Threshold Level (%)
Over torque
9-15
Activation Delay Time
(s)
Emotron AB 01-3990-11r3
Range/Code
0000: Electronic Motor Overload
Protection Set for Non-VSD Duty
Motor
0001: Electronic Motor Overload
Protection Set for VSD Duty Motor
0000: Constant Torque (OL=103%)
(150% for 1 Minute)
0001: Variable Torque (OL=113%)
(123% for 1 Minute)
0000: Coast-to-Stop After Overload
Protection is Activated
0001: Drive Will Not Trip when
Overload Protection is Activated
(OL1)
0000: Disable Over torque
Operation
0001: Enable Over torque
Operation Only if at Set Frequency
0002: Enable Over torque
Operation while the Drive is in Run
Mode
0000: Drive will Continue to
Operate After Over torque is
Activated
0001: Coast-to-Stop After Over
torque is Activated
30 to 200
0.0 to 25.0
Factory
Re-
setting
marks
0000
0000
0000
0000
0000
160
0.1
Software index