Max. Anzeigefehler: U
 ± 15 %, ELV U
n
-
Impedanz
(Innenwiderstand)
205 kΩ/ 5 kΩ
-
Stromaufnahme Messkreis: I
 < 6,0 mA (1.000 V)
s
-
Stromaufnahme Lastkreis: I
 < 550 mA (1.000 V)
s
-   Polaritätsanzeige: + 12 V LED, - 12 V LED 
-   Außenleiter- (Phasenanzeige) und Drehfeldprüfung: ≥ U
230 V, 50/60 Hz 
-   Durchgangsprüfung: 0 bis 100 kΩ, LED + Summer, Prüf-
strom: max. 10 μA
-   Kabelbruchdetektor: ≥ U
 200 V
n
-   Vibrationsmotor, Anlauf: ≥ U
 230 V 
n
-   Überspannungskategorie: CAT IV 600 V,  CAT 1000 V 
-   Schutzart: IP 65 (DIN VDE 0470-1 IEC/ EN 60529) 
 
6 - erste Kennziffer: Schutz gegen Zugang zu gefähr  l ichen 
Teilen und Schutz gegen feste Fremdkörper, staubdicht
 
5  -  zweite  Kennziffer:  Geschützt  gegen  Strahlwasser. 
Auch bei Niederschlägen verwendbar.
-   max. zulässige Einschaltdauer: 
 
ED = 30 s (max. 30 Sekunden), 240 s Pause 
-   Batterie: 2 x Micro, LR03/AAA (1,5 V) 
-
Gewicht: ca. 250 g
-   Verbindungsleitungslänge: ca. 1000 mm 
-
Betriebs- und Lagertemperaturbereich: - 15 °C bis + 55 °C
(Klimakategorie N) 
-   Relative Luftfeuchte: 20 % bis 96 % (Klimakategorie N) 
-   Rückregelzeiten:
Spannung/Zeit: 230 V/30 s, 400 V/9 s, 690 V/5 s, 1000 V/2 s.
Ansprechzeit der Anzeige (Eigenzeit): 750 ms

13. Allgemeine Wartung

Reinigen Sie das Gehäuse äußerlich mit einem sauberen tro-
ckenen Tuch.
Falls  Verunreinigungen  oder  Ablagerun  g en  im  Bereich  der 
Batterie oder des Batteriegehäuses vorhanden sind, reinigen
Sie auch diese mit einem tro ckenen Tuch.
Entfernen  Sie  bei  längerer  Lagerung  die  Batterien  aus  dem 
Gerät!

14. Umweltschutz

Bitte führen Sie verbrauchte Batterien und das Gerät
am Ende seiner Lebensdauer den zur Verfügung ste-
hen  d en Rückgabe- und Sammelsystemen zu.
Operating Manual
DUSPOL
expert
®
Before using the DUSPOL
expert voltage tester, proceed as
®
follows: Please read the operating manual and absolutely ob-
serve the safety instructions!
Table of Contents
1.
Safety instructions
2.
3.
voltage of an installation
4.
5.
6.
7.
8.
9.
11. Battery replacement
1.
Safety instructions:
-
During the use, touch the tester at the insulated handles
L1
7
and L2
8
only and do not touch the probe tips L1/-
2
3
!
-
Check the voltage tester for correct functioning immedi-
ately before and after using it in order to ensure the ab-
sence of voltage of an installation (see section 3). Do not
use the voltage tester, if one or more indications are not
working or if it does not seem to be ready for operation!
Please repeat the test with another voltage tester after-
wards.
-
With the battery being exhausted, the voltage tester is not
fully functional! From a voltage of AC/DC ≥ 50 V on, volt-
age tests are also possible without batteries by means of
the LED step indicator 
9
.
-
The voltage tester must be used only within the stated
nominal voltage range and in ele ctrical installations of up
to 1,000 V AC/DC!
-
The voltage tester must be used only in electric circuits of
overvoltage  category  CAT  III  with  max.  1,000  V  or  over-
voltage  category  CAT  IV  with  max.  600  V  for  phase-to-
earth measurements.
-
Do not operate the device with the battery compartment
being open.
-
The voltage tester is designed for being used by qualified
electricians and under safe working conditions.
-   The LED step indicator is intended for indicating the volt-
age range. It is not intended for measuring purposes.
-
Creating a voltage tester for more than 30 seconds volt-
age (maximum duty cycle = 30 s)!
-
Do not dismantle the voltage tester!
-
The voltage tester must be protected against contamina-
tion and damaging of the housing surface.
-
To protect them against damaging, provide the probe tips
with the enclosed probe tip protector
voltage tester!
-
Please observe that the impedance (internal resistance) of
10/2015
DUSPOL
expert
®
 + 0%, - 15%
n
Messkreis/
Lastkreis:
n
1
after using the
6