3 Transport and interim storage
When you receive the equipment, check that it has not been damaged during
transport. If you notice any defects, contact the carrier and follow the required
procedure within the specified timeframe.
CAUTION! The storage environment may cause damage!
If the equipment is to be installed at a later date, store it in a dry place and protect
it from impacts and external stresses (moisture, freezing temperatures, etc.).
4 Applications
An automatic control system for pumps designed for pumping and pressure
boosting of clean water or lightly contaminated water in the residential and
agricultural sectors.
Water supply from a well, cistern, other static water supply, municipal water mains,
etc. for the purposes of irrigation, sprinkling, pressure boosting, etc.
NOTE: The highest consumer should not be more than ~12 m above the HiControl
1 (Fig. 1).
5 Product Information
5.1 Technical data
Hydraulic data
Maximum operating pressure
Hydraulic connection diameter
Position of connection ports
Temperature range
Min/max fluid temperature
Min/max ambient temperature
Electrical data
Protection class
Max. current
Frequency
Voltage
Rated current
Working data
Pressure threshold below which the
pump will restart.
Flow rate threshold below which the
pump will stop.
Wilo SE
10 bar
1" male, screwed (DN25)
In line
+5°C/+60°C
+5°C/+60°C
IP 65
10 A
50/60 Hz
~220/240 V
1.9 A
1.5 bar
95 l/h
English