dixell XC807M Handleiding pagina 13

Electronische regelaar voor koelcentrales
Inhoudsopgave

Advertenties

F
Label
XC807M
XC811M
XC907M
XC911M
doF
5
5
donF
15
15
FdLy
No
no
FdLF
No
no
odo
20
20
LSE
-40.0
-40.0
HSE
10,0
10,0
StrS
0
0
SPrS
0
0
rSd1
No
no
rSd2
No
no
rSd3
No
no
rSd4
No
no
rSd5
No
no
rSd6
No
no
rSd7
No
no
UAro
Hours
Hours
Aro
255
255
PAo
30
30
LAL
15.0
15.0
HAL
20.0
20.0
tAo
20
20
SEr
9999
9999
PEn
5
5
PEI
15
15
CPP
1
1
SPr
2
2
PoPr
0
0
1
rELP
REL
rEL
Loc
No
no
dLI
0
0
4
Adr
1
1
PSo
0
0
nFn
3
4
PbC
Cur
Cur
P04
1
1
2
P20
31
31
2
CAL
0
0
SEP
1
1
PSc
0
0
dEU
°C
°C
Pbd
4.0
4.0
don
15
15
doF
5
5
rot
YES
YES
LSE
10,0
10,0
HSE
60
60
LAL
20,0
20,0
HAL
20,0
20,0
tAo
20
20
PEn
5
5
PEI
15
15
FPP
1
1
FPr
2
2
rELP
REL
rEL
PSo
0
0
Enkel zichtbaar als CtyP=0
1
3
Enkel zichtbaar als Cdn=no
Omschrijving
Time delay between switching off of two different compressors
Minimum time a stage stays ON
"don" delay enabled also for the first request
doF delay enabled also for the first switching off
Regulation delay with power on
Minimum set point (compressors)
Maximum set point (compressors)
Reduced set point start time
Reduced set point stop time
Enabling reduced set on Sunday
Enabling reduced set on Monday
Enabling reduced set on Tuesday
Enabling reduced set on Wednesday
Enabling reduced set on Thursday
Enabling reduced set on Friday
Enabling reduced set on Saturday
Measurement unit for the Aro parameter
Temporary alarm silencing
Alarm probe delay at power on
Minimum pressure alarm (compressors)
Maximum pressure alarm (compressors)
Low and High pressure (temperature) alarms delay
Running hours for maintenance
Max number of pressure-switch activation
Pressure-switch interventions time
Compressor management with faulty probe
Number of on compressors with faulty probe
Capacity engaged with faulty probe
Suction pressure displaying: relative or absolute
Keyboard lock
Sample rate for data logging
Serial address
Security code for operative parameters (compressors)
Configuratie parameters –Fans sectie
Number of fans
Kind of probe for condensing section
4mA readout (fans)
4mA readout (fans)
Condensing probe calibration
High pressure-switch polarity
Security code for configuration parameters (fans)
Werkingsparameters – Fans sectie
Default measurement unit for condensing section
Regulation band width (fans)
Time delay between the insertion of two different fans
Time delay between switching off of two different fans
Fans rotation enabling
Minimum set point (fans)
Maximum set point (fans)
Minimum pressure alarm (fans)
Maximum pressure alarm (fans)
Low and High pressure (temperature) alarms delay
Max number of pressure-switch activation
Pressure-switch interventions time
Fans management with faulty probe
Number of fans with faulty probe
Condensing pressure displaying: relative or absolute
Security code for operative parameters (fans)
Enkel zichtbaar als PbC=Cur
2
4
Enkel aanwezig in XC907M, XC911M
XC807_811M
handleiding
V:1.0 Data: 16/02/01
FRIGRO MOORSELE
PA04÷HSE with PbC = Cur; -50÷HSE with PbC = NTC
LSE÷PA20 with PbC = Cur; LSE÷110 with PbC = NTC
min, Hours
0.00÷(Set-PA04)
0.00÷(PA20-Set)
0 = Outputs on when alarm happens; 1 = Outputs
according to. SPr or PoPr parameters
AbS= absolute pressure; rEL=relative pressure
0÷255s (0=no recording)
0÷255 (0=security code disabled)
0÷6 (0=condensing section disabled)
Cur= 4÷20mA; ntC=NTC
0.00÷30.00bar
0.00÷40.00bar
-1.00÷1.00bar; -10.0÷10.0°C
0 =enabled without voltage; 1 =enabled with voltage.
0÷255(0=security code disabled)
bar=bar; °C=celsius
0.10÷5.00bar; 0.1÷30°C
no= fix sequence,
YES= with rotation
PA04÷HSE with PbC = Cur
-50÷HSE with PbC = NTC
LSE÷PA20 with PbC = Cur
LSE÷110 whit PbC = NTC
0.00÷(Set-PA04)
0.00÷(PA20-Set)
0 = fans on when alarm happens; 1 = Fans according to
AbS= absolute pressure; rEL= relative pressure
0÷255(0=esclusa)
Dixell s.r.l.
Z.I. Via dell'Industria, 27 - 32010 Pieve d'Alpago (BL) ITALY
tel. +39 - 0437 - 98 33 - fax +39 - 0437 - 98 93 13
http://www.dixell.com
E-mail: dixell@dixell.com
Bereik
0÷255s
0÷255s
no, YES
no, YES
0÷255s
0÷23h
0÷23h
no, YES
no, YES
no, YES
no, YES
no, YES
no, YES
no, YES
0÷255m/h
0÷255m
0÷255m
1÷9999h
0÷15
0÷15m
0÷CpnU
0÷255
no, YES
1÷247
0÷255s
0÷255s
0÷255m
0÷15
0÷15m
par. FPr
0÷nFn
Pa. 13 / 13