F
13. Parameters – Standaardinstellingen
Label
XC807M
XC811M
XC907M
XC911M
Set_N
-18,0
-18,0
Set_R
-18,0
-18,0
Set_N
35,0
35,0
Set_R
35,0
35,0
CPnU
4
7
CtyP
1
1
CPSt
1
1
PC1
0
0
1
PC2
0
0
1
PC3
0
0
1
PC4
0
0
1
PC5
0
0
1
PC6
0
0
1
PC7
0
0
1
PC8
-
0
1
PC9
-
0
1
rty
Db
db
Sty
Rt
rt
FtyP
r22
r22
PbC
Cur
cur
PA04
0,5
0,5
2
PA20
8,0
8,0
2
CAL
0
0
SEP
1
1
rSIP
1
1
LLI
1
1
ALIP
1
1
StPP
1
1
PSc
0
0
PrI
-
-
HoUr
-
-
dAy
-
-
ndAY
-
-
-
-
Mnth
YAr
-
-
dEU
°C
°C
Pbd
4.0
4.0
OnOn
5
5
OFOn
2
2
Cdn
YES
YES
don1
15
15
3
don2
15
15
3
don3
15
15
3
don4
15
15
3
don5
15
15
3
don6
15
15
3
don7
15
15
3
don8
-
15
3
don9
-
15
3
doF1
5
5
3
doF2
5
5
3
doF3
5
5
3
doF4
5
5
3
doF5
5
5
3
doF6
5
5
3
doF7
5
5
3
doF8
-
5
3
doF9
-
5
3
don
15
15

Omschrijving

Normal Set point; suction section
Reduced Set point; suction section
Normal Set point; condensing section
Reduced Set point; condensing section
Configuratie parameters - compressor sectie
Compressor Number
Compressor type
Compressor Step
Power of compressor 1
Power of compressor 2
Power of compressor 3
Power of compressor 4
Power of compressor 5
Power of compressor 6
Power of compressor 7
Power of compressor 8
Power of compressor 9
Type of regulation: neutral zone or proportional band
Sequence type
Freon Type
Type of probe (NTC - Current)
4mA readout (compressors)
20mA readout (compressors)
Probe Calibration (compressors)
Low pressure-switch polarity
Reduced set input polarity
Liquid level input polarity
Alarm input for compressors and fans polarity
Valve outputs polarity
Security code for configuration parameters (compressors)
Werkingsparameters - compressor sectie
Minutes
Hours
Day of month
Day of week
Month
Year
Displaying measurement unit
Regulation band width (compressors)
Minimum delay between 2 switching on of the same compressor
Delay between the switching off and on of the same compressor
don and doF equal for all the compressors
Time delay between the insertion of the compressor 1 and the following one
Time delay between the insertion of the compressor 2 and the following one
Time delay between the insertion of the compressor 3 and the following one
Time delay between the insertion of the compressor 4 and the following one
Time delay between the insertion of the compressor 5 and the following one
Time delay between the insertion of the compressor 6 and the following one
Time delay between the insertion of the compressor 7 and the following one
Time delay between the insertion of the compressor 8 and the following one
Time delay between the insertion of the compressor 9 and the following one
Time delay between the switching off of the compressor 1 and the following one
Time delay between the switching off of the compressor 2 and the following one
Time delay between the switching off of the compressor 3 and the following one
Time delay between the switching off of the compressor 4 and the following one
Time delay between the switching off of the compressor 5 and the following one
Time delay between the switching off of the compressor 6 and the following one
Time delay between the switching off of the compressor 7 and the following one
Time delay between the switching off of the compressor 8 and the following one
Time delay between the switching off of the compressor 9 and the following one
Time delay between the insertion of two different loads
XC807_811M
handleiding
V:1.0 Data: 16/02/01
FRIGRO MOORSELE
Bereik
LSE÷HSE
LSE÷HSE
LSE÷HSE
LSE÷HSE
0÷9
0÷1
1÷9
0÷255
0÷255
0÷255
0÷255
0÷255
0÷255
0÷255
0÷255
0÷255
db= neutral zone; Pb= proportional band
rt= rotation; F= fix sequence
r22 = R22; r404= R404a; 507= R507; 134=134
Cur= 0÷20mA; ntC=NTC
0.00÷30.00
0.00÷40.00
-1.00÷1.00bar; -10.0÷10.0°C
0 =enabled without voltage; 1 =enabled with voltage.
0 = enabled by opening; 1 =enabled by closing
0 =enabled without voltage; 1 =enabled with voltage.
0 =enabled without voltage; 1 =enabled with voltage.
0 =enabling by opening the relay; 1 = enabling by closing
the relay
0÷255 (0=no security code)
1÷59
0÷23
1÷31
Sun=Sunday; Mon=Monday; tuE=Tuesday;
Ued=Wednesday; thu=Thursday; Frd=Friday;
SAt=Saturday
0÷12
2000÷2099
bar= bar, °C=celsius
0.10÷5.00bar; 0.1÷30°C
0÷255m
0÷255m
no, YES
0÷255s
0÷255s
0÷255s
0÷255s
0÷255s
0÷255s
0÷255s
0÷255s
0÷255s
0÷255s
0÷255s
0÷255s
0÷255s
0÷255s
0÷255s
0÷255s
0÷255s
0÷255s
0÷255s
Pa. 12 / 13