STANDARD LIQUID/VAPOR RECOVERY PROCEDURE
7.
Connect the recovery unit to a right outlet. (See the nameplate on the
machine) Switch the power switch to the ON position, to start the
compressor.
8.
Slowly open the input port on the machine.
1)
If the compressor starts to knock, slowly throttle back the input valve
until the knocking stops.
2)
If the input valve was throttled back, it should be fully opened once the
liquid has been removed from the system (the manifold gauge set vapor
port should also be opened at this time).
9.
Run until desired vacuum is achieved.
1) Close the manifold gauge sets vapor and liquid ports.
2) Turn off the machine.
3) Close the unit's input port and proceed with the SELF –PURGE
PROCEDURE on the next page.
Note:
If the recovery machine fails to start, rotate the INPUT valve and the
MODE valve to purge position. Then rotate the MODE valve back
torecovery position, and open the INPUT valve.
Caution:
Always purge the unit after each use. Failure to purge the remaining
refrigerant from the unit could result in the acidic degradation of
internal components, ultimately causing premature.
.