STANDARD LIQUID/VAPOR RECOVERY PROCEDURE 
7.
Connect the recovery unit to a right outlet. (See the nameplate on  the 
machine)    Switch  the  power  switch  to  the  ON  position,    to  start  the 
compressor. 
8.
Slowly open the input port on the machine. 
1)
If the compressor starts to knock, slowly throttle back the input valve 
until the knocking stops. 
2)
If the input valve was throttled back, it should be fully opened once the 
liquid has been removed from the system (the manifold gauge set  vapor 
port should also be opened at this time). 
9.
Run until desired vacuum is achieved. 
1) Close the manifold gauge sets vapor and liquid ports. 
2) Turn off the machine. 
3) Close the unit's input port and  proceed with the SELF –PURGE 
PROCEDURE  on the next page. 
 
 
 
 
Note: 
 If the recovery machine fails to start, rotate the INPUT valve and the 
MODE valve to purge position. Then rotate the MODE valve back 
torecovery position, and open the INPUT valve. 
 
Caution: 
 
Always purge the unit after each use. Failure to purge the remaining 
refrigerant from the unit could result in the acidic degradation of 
internal components, ultimately causing premature. 
.
 
 