system. Use two high acid capacity filters, in series. When you have
finished recovering from the system, flush the recovery machine with a small
amount of clean refrigerant and refrigerant oil to purge off any foreign
substances left in the machine.
16.
This recovery machine has a Pressure Shut Off Switch. If the pressure
insi de the system should go above 38bars, the system will automatically shut
itself off. The shut off switch must be manually reset.
17.
If the tank pressure exceeds 20.7bar, use the TANK COOLING
PROCEDURE to reduce the tank pressure.
18.
To maximiz e recovery rates, use the shortest possible length of 3/ 8" or
larger hose. A hose no longer than 0.9meter is recommended
19.
When recovering large amounts of liquid, use the LIQUID PUSH
/PULL PROCEDURE.
20.
After recovering, make sure there's no refrigerant left in the machine.
Read the SELF ‐PURGING PROCEDURE carefully. Liquid refrigerant remained
may be expanded and destroy the components.
21.
If this recovery machine is to be stored or not used for any length of
time, we recommend that it be completely evacuated of any residual
refrigerant and purged with dry nitrogen.
22.
To reduce the risk of injury, care should be taken when moving this
machine.