In order for this procedure, you must have a minimum of 5 lbs.(2.3kg) of 
liquid refrigerant in the storage tank. 
 
1.
Connect the hoses as shown. 
2.
Turn the MODE valve to the Recover position. 
3.
Open the Vapor and Liquid valve of the storage tank. 
4.
Power on, and start the compressor. 
5.
Open the INPUT valve and OUTPUT valve of the machine. 
6.
     Throttle the OUTPUT valve of the machine  so that the  output pressure 
is 100psi greater than the input pressure, but never more than 300psi. 
7.
Run until tank is cold. 
 
 
 
All manuals and user guides at all-guides.com
TANK COOLING PROCEDURE 
 
9 EN
 
 
 
 
 
 
 