General safety regulations

WARNING DANGER:
Read, before you perform any action in connection with the tester, this
user manual carefully.Wabtec Netherlands is not liable for injuries,
(financial) damage and/or excessive wear resulting from incorrectly
performed maintenance, incorrect use of or modifications to the tester.
ATTENTION:
Under certain circumstances, in almost every electronic memory data
can be lost or changed. Therefore Wabtec Netherlands accepts no
financial responsibility for losses or claims by lost or otherwise unusable
information resulting from abuse, misuse, failure, neglect of the user
manual and procedures or other related causes.
ATTENTION:
The EazyPV red and black 4 mm test terminals may be used to make
measurements on circuits rated up to CAT III 300 VAC/DC with reference
to earth. Do not connect the EazyPV to voltages which may exceed
this rating.
ATTENTION:
The PV test terminals maximum rating: 1000 VDC open circuit voltage,
15 A short circuit current. Do not exceed this rating. The DC supply
must be isolated from earth during testing.
ATTENTION:
High voltages are present at the probe tips of the EazyPV during
insulation resistance measurement. Always hold test probes behind
the hand guards.
ATTENTION:
Check the EazyPV and all associated cables and leads before operating
the equipment. Do not use if there are signs of damage. Only use the
testleads supplied with the EazyPV.
ATTENTION:
Do not touch any exposed metal parts of the solar PV installation
during testing.
17