dIXEL
14. XLH260 CONNECTIES
H OT KEY
1 2
3 4 5 6 7 8 9 101 1 12 13
Conf. D oor
15. STANDAARDINSTELLINGEN
Label
Value
Menu
Set T
5.0
Set H
50.0
dbt
2.0
dbH
5.0
LS
-40
uS
110
odS
1
Ac
1
tHu
c-H
LSH
0.0
uSH
100.0
cF
°C
rES
dE
rEH
Hd
tdf
rE
EdF
in
SdF
0
dtE
8
idF
6
MdF
20
dFd
it
dAd
30
Fdt
0
dPo
no
Hud
no
Fnc
c-n
ALc
Ab
ALL
-40.0
ALu
110
ALH
1.0
ALd
15
dAo
1.3
EdA
20
dot
20
AHc
Ab
AHL
0.0
AHu
100
AHH
2.0
AHd
15
dHo
1.3
doH
20
nPS
20
XLH260_V1.doc
35 36
16 FLA (96L R A)
RS 485
(optionaal)
In
12V§
gnd
Input
4÷20mA
Description
- - -
Temperature Set Point
- - -
Humidity Set Point
Pr1
Half dead band width for temperature
Pr1
Half dead band width for humidity
Pr2
Minimum temperature set point limit
Pr2
Maximum temperature set point limit
Pr2
Outputs activation delay at start up
Pr1
Anti-short cycle delay
Pr2
Humidity regulation
Pr2
Minimum humidity set point limit
Pr2
Maximum humidity set point limit
Pr2
Measurement unit
Pr2
Resolution (for °C):
Pr2
Resolution for RH%:
Pr2
Defrost type
Pr2
Defrost mode
Pr2
Set point for SMART DEFROST
Pr2
Defrost termination temperature
Pr1
Interval between defrosts
Pr1
Duration of defrost
Pr2
Display during defrost
Pr2
Defrost display time out
Pr2
Draining time
Pr2
First defrost after start up
Pr2
Humidity control during defrost
Pr2
Fan operating mode
Pr2
Temperature alarm configuration
Pr1
Low temperature alarm setting
Pr1
High temperature alarm setting
Pr2
Temperature alarm recovery differential
Pr2
Temperature alarm delay
Pr2
Delay of temperature alarm at start-up
Pr2
Alarm delay at the end of defrost
Delay of temperature alarm after closing the
Pr2
door
Pr2
Humidity alarm configuration
Pr1
Low humidity alarm setting
Pr1
High humidity alarm setting
Pr2
Humidity alarm recovery differential
Pr2
Humidity alarm delay
Pr2
Delay of humidity alarm at start-up
Pr2
Alarm delay at the end of defrost
Pr2
Pressure switch number
Handleiding
20A 250V
16FLA(96 L RA )
20A 250V
16A
250V~
14
151 6 17 18
19 20
21 222 3 24 25 26
NC
Comp
Def
Hea ter
db = dehumidifier relay.; cHu = dehum+ compr.; c-H= without
XLH260
16A
8 A
8A
250V~
250V~
2 50V ~
2728
29 30 31
Line
L i g ht
NC
De-
Fa n
Hum
120/230V~
Hum
Range
LS ÷ uS ( nu = temperature regulation disabled )
LSH ÷ uSH ( nu = humidity regulation disabled)
0.1°C o 1°F ÷ 25°C o 77°F
0.5 ÷ 50
-50.0°C o –58°F ÷ Set T
Set T ÷ 110°C o 230°F
0 ÷ 250 min
0 ÷ 30 min
dehum. relay
Lci ÷ Set H
Set H ÷ uci
°C ÷°F
in = integer / dE = decimal
in = integer / Hd = half digit
rE, rT, in
In, Sd
-30 ÷ +30°C / -22÷+86°F
-50,0÷110°C/ -58÷230°F
1 ÷ 120 h
0 ÷ 250 min
rt / it / SEt / dEF / dEG
0 ÷ 250 min
0÷60 min.
n ÷ y
no; yES
c-n / c-Y / o-n / o-Y
rE = relative / Ab = absolute
0°C ÷ 50.0°C / -50.0°C ÷ ALu
0°C ÷ 50.0°C / ALL ÷ 110°C
0.1°C o 1°F ÷ 25°C o 77°F
0 ÷ 250 min
0.0 ÷ 23.5 h
0 ÷ 250 min
0 ÷ 250 min
rE = relative / Ab = absolute
0 ÷ 50 / Lci ÷ AHu
0 ÷ 50 / AHL ÷ uci
0.5 ÷ 25
0 ÷ 250 min
0.0 ÷ 23.5 h
0 ÷ 250 min
0÷15
cod. 1592017400
33 34
N
Supply
14/15