In case the Display of the control unit is off, make sure that the dip switch is
!
set to position "1" and not position "ON". The dip switch is present on the
main e-board inside the ColdStream unit.
6.2.1.1 Controller descriptions
Keeping pressed more than 1"sec., switches the cooling unit on or off.
Pressed once during setting On/Off periods, exits the menu.
Pressed once during modifying default parameters, exits the menu.
Keeping pressed more than 3"sec., if control unit is locked, makes it tempo-
rary unlocked.
In the OFF position, the Display shows:" oFF ". The panel is always powered
on.
Pressed once, displays the current fan speed (F1-F2-F3-FA).
Pressed once, gets into program selection or into On/Off periods setting.
Pressed once during On/Off periods setting, it has Enter function.
Keeping pressed more than 1"sec., selects operating mode: Cooling ON (ma-
nual), Cooling/Ventilation AUTO (automatic), Ventilation ON (manual).
If time is displaying, sets the current day.
Pressed once during On/Off periods setting, changes days.
Pressed till the display shows "time", it shows the current time setted.
If time is displaying, sets the current hour.
Pressed once during On/Off periods setting, changes hours.
Pressed once during modifying default parameters, increases the value.
Pressed once after pressing FAN command, increases fan speed and/or disa-
bles automatic fan speed.
Keeping pressed more than 2"sec. togheter with M command, changes the
default parameters.
If time is displaying, sets the current minutes.
Pressed once during On/Off periods setting, changes minutes.
Pressed once during modifying default parameters, decreases the value.
Pressed once after pressing FAN command, decreases fan speed and/or disa-
bles automatic fan speed.
Keeping pressed more than 2"sec. togheter with H command, changes de-
fault parameters.
Pressed once, shows the temperature detected.
Keeping pressed more than 5"sec., permits to set the temperature requested
(set-point).
Pressed once, shows the humidity detected.
Keeping pressed more than 5"sec., permits to set the humidity requested
(set-point).