7.2.4
CSA Certification Record
Certificate:
Class 2258 04
Class I, Div 1, Groups A, B, C and D;
Class II, Div 1, Groups E, F, and G,
Class III, Div 1, Enclosure Type 4X:
Model TZIDC-110, P/N V18346-x032x2xx0x Intelligent Positioner
Input rated
Intrinsically safe with entity parameters of:
Terminals 11 / 12
Terminals 85 / 86
Terminals 41 / 42
When installed per installation Drawing No 901265
Temperature Code
Max. Ambient
IMPORTANT (NOTE)
•
The "x" in P/N denotes minor mechanical variations or optional features.
•
Local communication interface LKS shall not be used in hazardous location.
•
Each pair of conductors of each intrinsic safety circuit shall be shielded.
CI/TZIDC/110/120-NL
V max = 24 V
I max = 250 mA
C
= 2.8 nF
i
L
= 7.2 uH
i
U max = 30 V
I max = 50 mA
C
= 3.8 nF
i
L
= 0 uH
i
U max = 16 V
I max = 20 mA
C
= 60 nF
i
L
= 100 uH
i
TZIDC, TZIDC-110, TZIDC-120
Ex-relevante technische gegevens
1649904 (LR 20312)
PROCESS CONTROL EQUIPMENT –
Intrinsically Safe, Entity – For Hazardous
Locations
32 V DC; max. 15 mA (powered by a SELV
Circuit)
T4
85 Deg C
47