7.1.4

CSA Certification Record

Certificate:
Class 2258 04
Class I, Div 1, Groups A, B, C and D;
Class II, Div 1, Groups E, F, and G,
Class III, Div 1, Enclosure Type 4X:
Model TZIDC, P/N V18345-x0x2x2xx0x Intelligent Positioner
Input rated
Output pressure
Intrinsically safe with entity parameters of:
Terminals 11 / 12
Terminals 81 / 82
Terminals 83 / 84
Terminals 31 / 32
Terminals 41 / 42 and
51 / 52
Terminals Limit2 41 / 42 and
Limit1 51 / 52
When installed per installation Drawing No 901064
Temperature Code
Max. Ambient
IMPORTANT (NOTE)
The "x" in P/N denotes minor mechanical variations or optional features.
Local communication interface LKS shall not be used in hazardous location.
Each pair of conductors of each intrinsic safety circuit shall be shielded.
CI/TZIDC/110/120-NL
V max = 30 V
I max = 104 mA
C
= 6.6 nF
i
L
= 0 uH
i
V max = 30 V
I max = 110 mA
C
= 3.7 nF
i
L
= 0 uH
i
V max = 30 V
I max = 96 mA
C
= 3.7 nF
i
L
= 0 uH
i
V max = 30 V
I max = 110 mA
C
= 6.6 nF
i
L
= 0 uH
i
V max = 30 V
I max = 96 mA
C
= 3.7 nF
i
L
= 0 uH
i
V max = 15.5 V
I max = 52 mA
C
= 20 nF
i
L
= 30 uH
i
TZIDC, TZIDC-110, TZIDC-120
Ex-relevante technische gegevens
1649904 (LR 20312)
PROCESS CONTROL EQUIPMENT –
Intrinsically Safe, Entity – For Hazardous
Locations
30 V DC; max.4 ... 20 mA
Max. 90 psi
T4
85 Deg C
37