Especially if the flue runs through unheated room s or outside the house, further
insulat ion is necessary. Metal chimneys, or parts of the chimney outside heated
rooms should always have double- walled, insulated flues. The part of the chim-
ney outside the roof should always be insulat ed.
The chim ney should be high enough (at least four met res) and should end in a
zone that is clear of nearby buildings, trees or other obstacles. The rule of
thum b here is: 60 cm above the ridge of the roof. If the distance bet ween the
ridge and the chim ney m easures m ore than three m etres, see the dim ensions
stipulated in the illustrat ion below. Depending on the presence of nearby build-
ings or t rees, the chimney should be higher.

3.1.2. Ventilation

The burning of wood, charcoal or gas involves ox ygen consumption. It is of the ut-
most importance that the room in which the stove is installed should be sufficient ly
ventilated.
Insufficient ventilation m ay disrupt the com bustion process and cause the sm oke
flow through the chimney to be interrupted, which m ay lead to sm oke em issions
into the room .
If necessary, you can install a ventilation grille to provide a constant flow of fresh air
in the room. This precaut ion is particularly necessary in well- insulated rooms with
mechanical ventilation.
Ensure not to use other air- consum ing appliances, such as heaters, cooking hoods,
bathroom ventilators, in the sam e room or in the house while the stove is burning;
or m ake sure t o have an ex tra ventilation grill installed for these appliances.
If your appliance is provided with a connection kit for supplying the com bustion air
from outside the room, you do not need to provide your appliance with any ex tra air
intake.
Ensure that there is sufficient ventilation in the area from which you draw the air.

3.1.3. Floor, walls

A safe distance should be kept between the stove and com bustible m at erials such as
wooden walls and furniture. This distance should be at least forty cent im etres for
the side- wall and 30 cm for the back- wall.
The appliance shall be installed on floors with an adequate load- bearing capacit y.
Com bustible floors require sufficient protect ion against radiant heat by m eans of a
fireproof protective plate. Rugs and carpets must be kept at a distance of at least
eighty centim et res from the fire.
Astroline 2
highest point of the roof
within a distance of 3 m.
24
3 m
3 m
min 0.5 m
min 0.5 m
min 1 m