Stuurkaart digitale/pulsingangen:
- Aantal programmeerbare digitale ingangen .................................................................................................... 4
- Klemnummers ...................................................................................................................... X101-2, -3, -4, -5
- Spanningsniveau ........................................................................................ 0 - 24 V DC (PNP positieve logica)
- Spanningsniveau, logische ´0´ ........................................................................................................... < 5 V DC
- Spanningsniveau, logische ´1´ ......................................................................................................... > 10 V DC
- Maximum ingangsspanning ................................................................................................................ 28 V DC
- Ingangsweerstand, R
.............................................................................................................. ongeveer 2 kΩ
i
- Scan-tijd ........................................................................................................................................... 20 msec
Stuurkaart, pulsingang:
- Aantal programmeerbare pulsingangen ........................................................................................................ 1
- Klemnummers ....................................................................................................................................... X101-3
- Max. frequentie op klem 3, open collector/balans 24 V ............................................................ 8 kHz/70 kHz
- Resolutie ................................................................................................................................................. 10 Bit
- Nauwkeurigheid (0,1-1 kHz), klem 3 ................................................... Max. fout 0,5 % van volledige schaal
- Nauwkeurigheid (1-12 kHz), klem 3 ..................................................... Max. fout 0,1 % van volledige schaal
Stuurkaart, analoge ingangen:
- Aantal programmeerbare analoge spanningsingangen ................................................................................ 1
- Klemnummers ....................................................................................................................................... X101-2
- Spanningsniveau ....................................................................................................... 0 - 10 V DC (schaalbaar)
- Ingangsweerstand, R
............................................................................................................ ongeveer 10 kΩ
i
- Aantal programmeerbare analoge stroomingangen ....................................................................................... 1
- Klemnummer ........................................................................................................................................ X101-1
- Stroombereik ............................................................................................................... 0 - 20 mA (schaalbaar)
............................................................................................................ ongeveer 300 Ω
- Ingangsweerstand, R
i
- Resolutie ................................................................................................................................................... 9 Bit
- Nauwkeurigheid bij ingang ....................................................................... Max. fout 1 % van volledige schaal
- Scan-tijd .............................................................................................................................................. 20 sec.
Stuurkaart, digitale/puls- en analoge uitgangen:
- Aantal programmeerbare digitale en analoge uitgangen .............................................................................. 1
- Klemnummers. ...................................................................................................................................... X101-9
- Spanningsniveau bij digitale uitgang/belasting .................................................................. 0 - 24 V DC/25 mA
- Stroom bij analoge uitgang .............................................................................................................. 0 - 20 mA
- Maximumbelasting op frame (klem 8) bij analoge uitgang .................................................. R
- Nauwkeurigheid van analoge uitgang .................................................. Max. fout 1,5 % van volledige schaal
- Resolutie op analoge uitgang. ................................................................................................................... 8 Bit
Stuurkaart, RS 485 seriële communicatie:
- Klemnummers ................................................................................................................................. X100-1, -2
Stuurkarakteristieken (frequentie-omvormer):
- Frequentiebereik .............................................................................................................................. 0 - 132 Hz
- Resolutie op uitgangsfrequentie ............................................................................................................. 0,1 %
- Systeemresponstijd ................................................................................................................. Max. 40 msec.
MG.03.B6.10 - VLT is een geregistreerd handelsmerk van Danfoss
FCM Serie 300
≤ 500 Ω
BELASTING
15