Netvoeding (L1, L2, L3)
Netvoeding (L1, L2, L3):
Voedingsspanning 200-240 V-eenheden ......................................................... 3 x 200/208/220/230/240 V ±10 %
Voedingsspanning 380-460 V-eenheden ......................................................... 3 x 380/400/415/440/460 V ±10 %
Voedingsspanning 525-600 V-eenheden ................................................................ 3 x 525/550/575/600 V ±10 %
Netfrequentie .................................................................................................................................. 48-62 Hz ± 1%
Max. onbalans van de netspanning:
VLT 6002-6011, 380-460 V en 525-600 V en VLT 6002-6005, 200-240 V .... ±2,0 % van de nominale netspanning
VLT 6016-6072, 380-460 V en 525-600 V en VLT 6006-6032, 200-240 V .... ±1,5 % van de nominale netspanning
VLT 6102-6602, 380-460 V and VLT 6042-6062, 200-240 V ....................... ±3,0 % van de nominale netspanning
VLT 6102-6402, 525-600 V ............................................................................ ±3 % van de nominale netspanning
Werkelijke arbeidsfactor (λ) ............................................................................ 0,90 nominaal bij nominale belasting
Verschuivingsfactor (cos. ϕ) .............................................................................................. dicht bij eenheid (>0,98)
Aantal schakelingen bij netingang L1, L2, L3 ..................................................................... ongeveer 1 keer/2 min.
Max. nominale kortsluitingsstroom ......................................................................................................... 100,000 A
VLT-uitgangsgegevens (U, V, W):
Uitgangsspanning ............................................................................................. 0-100 % van de voedingsspanning
Uitgangsfrequentie:
Uitgangsfrequentie 6002-6032, 200-240 V ........................................................................... 0-120 Hz, 0-1000 Hz
Uitgangsfrequentie 6042-6062, 200-240 V ............................................................................. 0-120 Hz, 0-450 Hz
Uitgangsfrequentie 6002-6062, 380-460 V ........................................................................... 0-120 Hz, 0-1000 Hz
Uitgangsfrequentie 6072-6602, 380-460 V ............................................................................. 0-120 Hz, 0-450 Hz
Uitgangsfrequentie 6002-6016, 525-600 V ........................................................................... 0-120 Hz, 0-1000 Hz
Uitgangsfrequentie 6022-6062, 525-600 V ............................................................................. 0-120 Hz, 0-450 Hz
Uitgangsfrequentie 6072, 525-600 V ...................................................................................... 0-120 Hz, 0-450 Hz
Uitgangsfrequentie 6102-6352, 525-600 V ............................................................................. 0-132 Hz, 0-200 Hz
Uitgangsfrequentie 6402, 525-600 V ...................................................................................... 0-132 Hz, 0-150 Hz
Nominale motorspanning, 200-240 V-eenheden ............................................................... 200/208/220/230/240 V
Nominale motorspanning, 380-460 V-eenheden ............................................................... 380/400/415/440/460 V
Nominale motorspanning, 525-600 V-eenheden ............................................................................. 525/550/575 V
Nominale motorfrequentie ........................................................................................................................ 50/60 Hz
Schakelen aan uitgang ........................................................................................................................... Onbeperkt
Aan- en uitlooptijden ................................................................................................................................ 1-3600 s
Koppelkarakteristieken:
Startkoppel ....................................................................................................................... 130 % gedurende 1 min
Startkoppel (parameter 110 Hoog losbreekkoppel) ...................................... Max. koppel: 160 % gedurende 0,5 s
Versnellingskoppel ........................................................................................................................................ 100%
Overbelastingskoppel ................................................................................................................................... 110%
Stuurkaart, digitale ingangen:
Aantal programmeerbare digitale ingangen ........................................................................................................... 8
Klemnrs. ................................................................................................................... 16, 17, 18, 19, 27, 29, 32, 33
Spanningsniveau .............................................................................................................. 0- 24 V DC (PNP logica)
Spanningsniveau, logische
Spanningsniveau, logische
Maximumspanning op ingang ................................................................................................................... 28 V DC
Ingangsweerstand, R
.................................................................................................................................... 2 k
i
Scantijd per ingang .................................................................................................................................... 3 msec.
MG.61.B3.10 - VLT is een geregistreerd handelsmerk van Danfoss
0 .................................................................................................................... < 5 V DC
´
1 ................................................................................................................... >10 V DC
´
®
VLT
Serie 6000 HVAC