INSTALLATIE
AC ingang
L 1 N P E
Afb. 2: Aansluitingen kast 2.
DIP SWITCH SETTINGS
4
3
2
1
dip switches
0
0
0
0 :
Standard
1
0
0
0 :
Diode
0
1
0
0 :
Gel
1
1
0
0 :
Diode + Gel
0
0
1
0 :
Traction
1
0
1
0 :
Traction + Diode
0
1
1
0 :
ContMon + Traction
1
1
1
0 :
ContMon + Traction + Diode
0
0
0
1 :
ForceFloat
1
0
0
1 :
ForceFloat + Diode
0
1
0
1 :
ForceFloat + Gel
1
1
0
1 :
ForceFloat + Diode + Gel
0
0
1
1 :
ContMon
1
0
1
1 :
ContMon + Diode
0
1
1
1 :
ContMon + Gel
1
1
1
1 :
ContMon + Diode + Gel
AC aansluitingen
3-24/100 lader.
AC input
L1 L2 L3 PE
L1 N
AC input
Afb. 3: Aansluitingen kast 3.
6
temp. sensor
4 3 2 1
RS 485
RS 232 ANALOG
+s
-s
NO
C
+ 3A
+
NC
Only for:
12/60-2
12/80-2
24/50-2
1 = on; 0 = off
ContMon:
Continuous monitor mode. The µP and the RS485/RS232/DC
alarm stays functioning at mains failure. The auxiliary power
goes down but the remotes stay functioning if remote has own
power source.
Diode:
Diode compensation on (+0.6V).
Gel:
Gel compensation on (+0,55V during float) or 1.1V/24V or 2.2V/
48V.
Traction:
Traction charging (+0.7V during bulk and +0.4V in absorption).
Force float: One step charge programme with fixed float voltage.
RS 485
RS 232
Juli 2001 / MASS acculaders "Colorado" C2 & C3 / NL
+ SENSE
- SENSE
N.O.
COMMON
N.C.
temp. sensor
+s
ANALOG
- s
NO
C