9.4 Modbus-parameters
Naam
005.T_setpoint
006.T_min
007.T2_min
008.Timer
009.Start_HP_Hour
010.Start_HP_Min
011.Stop_HP_Hour
012.Stop_HP_Min
013.H_pump
014.Legionel_Auto_function
015.Wwprotec
016.FanOper *
017.FanCon *
018.Solacel
019.SC_HP
020.SC_EL
021.Holiday
022.Man_days_set
023.Boost
024.FanPause *
026.Language
027.Defrost
(niet veranderen)
028.Anode *
029.T_max
44 | WOLF GmbH
Read Holding Register (4x)
Een-
Modbus Address
heid
°C
(T instel)
°C
(T min)
(T2 min)
°C
(Timer)
AanUit
(h_klok)
Uur
Min
(m_klok)
Uur
(h_stop)
(h_stop)
Min
(Bedr.modus)
(T Legio)
°C
(Tmin RL)
(WP_LS)
(KWL)
(PV.modus)
(T.PV_WP)
°C
(T.PV_EL)
°C
(vakantie)
Dagen
(Afw dagen)
(Boost)
AanUit
(VenPauze)
(taal)
(ontdooiing)
(anode)
AanUit
°C
(T max)
Min
Max
4
5
62
5
5
62
6
5
62
7
0
1
8
0
23
9
0
59
10
0
23
11
0
59
12
0
5
13
0
2
14
5
20
15
0
1
0
3
16
0
2
17
0
3
18
5
62
19
5
62
20
0
5
21
1
99
22
0
1
23
0
6
25
0
10
26
0
2
27
0
1
28
5
62
Decimal
Offset Remarks
0
0
0
0
0
0
0
0
0 = Off
1 = On
0
0
0
0
0
0
0
0
0
0
0 = Off
1 = Alleen HP
2 = Alleen EL
3 = HP + EL
4 = Ketel
5 = HP + Ketel
0
0
0 = Off
1 = 60°C
2 = 65°C
0
0
0
0
0 = Low (AC fan only)
1 = High (AC fan only)
0
0
0 = Off (EC Fan only)
1 = EC Low (EC Fan only)
2 = EC Mid (EC Fan only)
3 = EC High (EC Fan only)
0
0
0 = Off
1 = EC Low
2 = EC Mid
3 = EC High
0
0
0 = Off
1 = Alleen HP
2 = Alleen EL
3 = HP + EL
0
0
0
0
0
0
0 = Off
1 = 1 Week
2 = 2 Weken
3 = 3 Weken
4 = 3 Dagen
5 = Manueel
0
0
0
0
0
0
0 = Off
1 = 30m/15s
1 = 30m/30s
1 = 60m/15s
1 = 60m/30s
1 = 90m/15s
1 = 90m/30s
0
0
0 = English
1 = German
2 = French
3 = Nederlands
4 = Spanish
5 = Italian
6 = Danish
7 = Swedish
8 = Norwegian
9 = Polish
10 = Slovenian
11 = Croatian
0
0
0 = Air
1 = Gas
2 = Tmin RF
0
0
0
0
9148388_202204