TABLE "B" - LOGIC MENU - (logic)
Logic
Default
Set the type of motor
OTOR type
0
Automatic Closing
TCA
0
0
FAST CLS.
STEP-BY-STEP
0
OVE NT
0
PRE-ALAR
0
HOLD-TO-RUN
0
IBL OPEN
during opening
0
|IBL TCA
0
PRESS SWC
switch pressure
0
1 motor active
1
OT. on
OPEN
0
IN OTHER
DIRECT.
Configuration of
safety input SAFE
0
SAFE 1
Configuration of
safety input SAFE
6
SAFE 2
https://alborzsanat.com
INSTALLATION MANUAL
Cross out
Definition
setting
Description
used
0
Motors not active
Motor type
1
ELI 250 BT
connected to the
2
PHOBOS BT
board.
3
IgEA BT
0
Logic not enabled
Time
Switches automatic closing on
1
0
Logic not enabled
Fast closing
1
Closes 3 seconds after the photocells are cleared before waiting for the set TCA to elapse.
Inputs configured as Start E, Start I, Ped
0
operate with 4-step logic.
Inputs configured as Start E, Start I, Ped
1
operate with 3-step logic. Pulse during
Step-by-step
closing reverses movement.
movement
Inputs configured as Start E, Start I, Ped
2
operate with 2-step logic. Movement
reverses with each pulse.
0
The flashing light comes on at the same time as the motor(s) start.
Pre-alarm
1
The flashing light comes on approx. 3 seconds before the motor(s) start.
0
Pulse operation.
Deadman mode.
Input 61 is configured as OPEN UP.
Input 62 is configured as CLOSE UP.
1
Operation continues as long as the OPEN UP or CLOSE UP keys are held down.
Deadman
Emergency Deadman mode. Usually pulse operation.
If the board fails the safety device tests (photocell or safety edge, Er0x) 3 times in a row, the device
is switched to Deadman mode, which will stay active until the OPEN UP or CLOSE UP keys are
released.
2
Input 61 is configured as OPEN UP.
Input 62 is configured as CLOSE UP.
Block pulses
0
Pulse from inputs configured as Start E, Start I, Ped has effect during opening.
1
Pulse from inputs configured as Start E, Start I, Ped has no effect during opening.
0
Pulse from inputs configured as Start E, Start I, Ped has effect during TCA pause.
Block pulses
during TCA
1
Pulse from inputs configured as Start E, Start I, Ped has no effect during TCA pause.
Movement is stopped only when the closing limit switch trips: in this case, the tripping of the
0
closing limit switch must be adjusted accurately (Fig.g Ref.B).
Use when there is a mechanical stop in closed position. This function allows leaves to press against
Closing limit
the mechanical stop without the Amperostop sensor interpreting this as an obstacle. Thus the
1
rod continues its stroke for a few seconds after meeting the closing limit switch or as far as the
mechanical stop. In this way, the leaves come to rest perfectly against the stop by allowing the
closing limit switches to trip slightly earlier (Fig.g Ref.A).
0
Both motors active (2 leaves).
1
Only motor 1 active (1 leaf ).
0
Standard operating mode (See Fig.g Ref.C).
Open in other
direction
1
Opens in other direction to standard operating mode (See Fig.g Ref.D).
0
Input configured as Phot (photocell).
1
Input configured as Phot test (tested photocell).
2
Input configured as Phot op (photocell active during opening only).
3
Input configured as Phot op test (tested photocell active during opening only).
4
Input configured as Phot cl (photocell active during closing only).
1.
5
Input configured as Phot cl test (tested photocell active during closing only).
72
6
Input configured as Bar, safety edge.
7
Input configured as Bar, tested safety edge.
Input configured as Bar 8k2.
8
0
Input configured as Phot (photocell).
1
Input configured as Phot test (tested photocell).
2
Input configured as Phot op (photocell active during opening only).
3
Input configured as Phot op test (tested photocell active during opening only).
4
Input configured as Phot cl (photocell active during closing only).
2.
5
Input configured as Phot cl test (tested photocell active during closing only).
74
6
Input configured as Bar, safety edge.
7
Input configured as Bar, tested safety edge.
8
Input configured as Bar 8k2.
WARNING: safety devices are not enabled.
WARNING: with the device set to Emergency Deadman mode, safety devices are not
enabled.
step-by-step mov.
2 STEP
3 STEP
CLOSED
OPENS
OPENS
DURINg
CLOSINg
OPEN
CLOSES
CLOSES
DURINg
STOP + TCA STOP + TCA
OPENINg
AFTER STOP
OPENS
OPENS
4 STEP
OPENS
STOPS
CLOSES
OPENS
25
THALIA -