Probe
1. Remove the probe from the container for leak detection fluid.
- The red LED lights.
- The audible alarm sounds.
2. Refit the probe into the container for leak detection fluid.
- The audible alarm and the visual alarm must switch off automatically.
Control unit
1. Press the Test key.
- The red LED lights up and the audible alarm sounds.
Release the Test key to terminate the function test at the control unit.
Container for leak detection fluid
Check the level of the leak detection fluid and refill leak detection fluid up to
the test opening, if required.
6.4

Commissioning the product

 Verify that the product has been properly mounted and electrically con-
nected.
1. Apply voltage via the on-site mains fuse.
- The green LED is on.
2. Perform the function test.
Commissioning
LAG-14 ER
EN
37