5.3

Mounting connection line(s)

UNSUITABLE CONNECTION LINES AND FITTINGS

Zinc can react with leak detections fluids.
Verify that the leak detection fluid cannot come into contact with zinc.
Failure to follow these instructions can result in equipment damage.

INCORRECT FASTENING

The leak detection fluid container must not be fastened to the connection line.
Ensure that the container for leak detection fluid is fastened to a wall or other
support.
Failure to follow these instructions can result in equipment damage.
The connection line must have a steady gradient towards the tank; it must not
be possible to shut it off.
Mounting
NOTICE
NOTICE
LAG-14 ER
EN
24