19.3 Feeding the cable and installing it with strain relief
Feed the power cable through the protective casing pipe.
Avoid making it too long. Fit the cable clamp around the cable and fix it in place (3 Nm max).
(diagram 1.1)
19.4 Connecting the power cable to the terminals
Connect the phase conductors to the terminals marked L1 / L2 / L3 (4-5 Nm)
Connect the neutral conductor to the neutral terminal (blue)(4-5 Nm).
Connect the grounding conductor to the coded ground terminal (green)
Diagram 1.1
Plug connec on type 2
IEC 61815-1 VDE-AR-E2623-2-2
Pa ern load separator
Central grounding point
4 moun ng holes for moun ng the casing
on the founda on
24. www.ecotap.nl
RCD
Fuses
(4-5 Nm).
Transparant plas c cap
May only be removed by Ecotap B.V.
Or authorised personnel
Magne c switch
Kilowa hour meter MID cer fied
Transparant plas c lid
to be sealed with seal closure*
35mm2 terminals
Strain relief for protec ve casing and
power cable
Robust casing 40mm²
*
01-05-23