PEFY-P-VMR-E-L/R series
Item
Power source
Cooling capacity*1/Heating capacity*1
Dimension
Height / Width / Depth
Net weight
Airflow rate (Low-Middle-High)
Fan
External static pressure
Noise level (Low-Middle-High)*3
Filter
PEFY-P-VMA(L)-E series
Item
Power source
Cooling capacity*1 / Heating capacity*1
Dimension
Height / Width / Depth
Net weight
Airflow rate (Low-Mid-High)
Fan
External staticpressure*2
Sound level
(measurement condition 1) dB(A)
(Low-Mid-High)*3 (measurement condition 2) dB(A)
Filter
Item
Power source
Cooling capacity*1 / Heating capacity*1
Dimension
Height / Width / Depth
Net weight
Airflow rate (Low-Mid-High)
Fan
External staticpressure*2
Sound level
(measurement condition 1) dB(A)
(Low-Mid-High)*3 (measurement condition 2) dB(A)
Filter
Item
Power source
Cooling capacity*1 / Heating capacity*1
Dimension
Height / Width / Depth
Net weight
Airflow rate (Low-Mid-High)
Fan
External staticpressure*2
Sound level
(measurement condition 1) dB(A)
(Low-Mid-High)*3 (measurement condition 2) dB(A)
Filter
Notes: * Operation temperature of indoor unit.
Cooling mode: 15 °C WB - 24 °C WB
Heating mode: 15 °C DB - 27 °C DB
*1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling: Indoor: 27 °C DB/19 °C WB
Heating: Indoor: 20 °C DB
*2 The external static pressure is set to 50 Pa at factory shipment.
*3 The operating noise is the data that was obtained in an anechoic room.
18
Model
P20VMR-E-L/R
~220-240V 50Hz/~220-230V 60Hz
kW
2.2/2.5
mm
292/640/580
kg
18
m
3
/min
4.8/5.8/7.9
Pa
5
220V
20/25/30
dB(A)
230V
21/26/32
240V
22/27/30
Model
P20VMA(L)-E
kW
2.2/2.5
mm
250/700/732
kg
23
3
/min
m
6.0-7.5-8.5
Pa
35/50/70/100/150
23-25-26
26-28-29
Model
P63VMA(L)-E
kW
7.1/8.0
mm
250/1100/732
kg
32
m
3
/min
13.5-16.0-19.0
Pa
35/50/70/100/150
25-29-33
29-32-36
Model
P100VMA(L)-E
kW
11.2/12.5
mm
250/1400/732
kg
42
m
3
/min
23.0-28.0-33.0
Pa
35/50/70/100/150
28-33-37
32-37-41
Outdoor: 35 °C DB
Outdoor: 7 °C DB/6 °C WB
P25VMR-E-L/R
P32VMR-E-L/R
2.8/3.2
3.6/4.0
292/640/580
292/640/580
18
18
4.8/5.8/7.9
4.8/5.8/9.3
5
5
20/25/30
20/25/33
21/26/32
21/26/35
22/27/30
22/27/33
Standard filter
P25VMA(L)-E
P32VMA(L)-E
220-240V 50/60Hz
2.8/3.2
3.6/4.0
250/700/732
250/700/732
23
23
6.0-7.5-8.5
7.5-9.0-10.5
35/50/70/100/150
35/50/70/100/150
23-25-26
23-26-29
26-28-29
28-30-34
Standard filter
P71VMA(L)-E
P80VMA(L)-E
220-240V 50/60Hz
8.0/9.0
9.0/10.0
250/1100/732
250/1100/732
32
32
14.5-18.0-21.0
14.5-18.0-21.0
35/50/70/100/150
35/50/70/100/150
26-29-34
26-29-34
30-34-38
30-34-38
Standard filter
P125VMA(L)-E
P140VMA(L)-E
220-240V 50/60Hz
14.0/16.0
16.0/18.0
250/1400/732
250/1600/732
42
46
28.0-34.0-40.0
29.5-35.5-42.0
35/50/70/100/150
35/50/70/100/150
32-36-40
33-37-42
35-40-44
36-41-45
Standard filter
P40VMA(L)-E
P50VMA(L)-E
4.5/5.0
5.6/6.3
250/900/732
250/900/732
26
26
10.0-12.0-14.0
12.0-14.5-17.0
35/50/70/100/150
35/50/70/100/150
23-27-30
25-29-32
28-30-34
28-32-35
measurement condition 1
Aux. duct
2m
2m
Measurement location
measurement condition 2
Aux. duct
test unit
2m
1m
Measurement location