Download Inhoudsopgave Inhoud Print deze pagina

Electrical Wiring; Control-Box; Photoresistance; Pin Plug - Riello Burners Gulliver RG1R Installatie-, Gebruiks- En Onderhoudsvoorschriften

Inhoudsopgave

Advertenties

3.4 ELECTRICAL WIRING

WARNING
DO NOT EXCHANGE NEUTRAL WITH PHASE
~
50Hz 230V
PE L
N
Limit thermostat
with manual
resetting

7 pin plug

7 pole socket
D1912
Ignition
electrodes
CONTROL BOX
To remove the control-box from the burner, loosen screw (A, fig. 9)
and pull to the arrow direction, after removing all components, the
7 pin plug and earth wire.
In case of disassembly of the control box, retighten the screw
(A) with a torque wrench setting of 1 – 1.2 Nm.
2304
Main switch
T6A
Regulating
thermostat
Brown
Blue
Black
White
Blue
Heater with start
Burner-earth
NOTES:
– Wires of 1 mm
– The electrical wiring carried out by the installer
must be in compliance with the rules in force in
the Country.
Hour counter
(230V - 0.1A max.)
Remote lock-out lamp
(230V - 0.5A max.)

Photoresistance

Oil valve
Motor
thermostat
5
GB
2
section
.
TESTING
Check the shut-down of the burn-
er by opening the thermostats and
the lock-out by darkening the
photoresistance.
Capacitor
S7186
Fig. 9
A

Advertenties

Inhoudsopgave
loading

Deze handleiding is ook geschikt voor:

3736450

Inhoudsopgave